6.1 Mechanical Engineering

Click the cells below to choose a level of standard for each attribute. Show Tooltips

IN THIS SECTION:  Temperature  |  Humidity Control  |  Air Movement  |  Pressure  |  Ventilation  |  Filtration  |  Acoustics  |  Operational Efficiency
Maintainability  |  Operability  |  Service Life

AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Temperature
ReferenceASHRAE 55-2010ASHRAE 55-2010ASHRAE 55-2010ASHRAE 55-2010ASHRAE 0
ASHRAE 1.1
SMACNA
ASHRAE 0
ASHRAE 1.1
Performance75±2°F cooling, 72±2°F heating, Allowance for unoccupied hour setup and setback optimized with re-occupancy pick-up and pull-down energy demands within a range of 55°F to 83°F,Thermal zones limited to 300 sf at the perimeter 15' and 1500 sf interiorBaseline features and add control or provide that surface temperatures are ±7°F of the air temperature,Thermal zones limited to 300 sf at the perimeter 15' (or no more than 1 private office) and 800 sf interior★ features and add control or provide that surface radiant temperatures are ±2°F of the air temperature, or inversely offset expanded air temperature ranges and do not form condensation.★★ and individual occupant controlled surface radiant temperatures and optimized air at 75-80°F cooling 65-72°F heatingBaseline: No
★: No
★★: Yes
★★★: Yes
Baseline: Yes
★: Yes
★★: Yes
★★★: Yes
Provide calculations of the transient coupled one-dimensional heat and moisture transport in multi-layer building components exposed to natural weather using WUFI-ORNL/IBP for each construction condition.Show proposed zoning and corresponding square footage for all conditioned spaces. Show temperature range for each zone and interior surface temperatures, when applicable.After occupancy, provide 2 weeks of 15 minute trend history of space and surface temperature (when controlled).
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Humidity Control
ReferenceASHRAE 55-2010, graphic comfort zone methodASHRAE 55-2010, Michalski (1998), 2011 ASHRAE Handbook – HVAC ApplicationsASHRAE 55-2010, Michalski (1998), 2011 ASHRAE Handbook – HVAC ApplicationsASHRAE 55-2010, Michalski (1998), 2011 ASHRAE Handbook – HVAC ApplicationsASHRAE 0
ASHRAE 1.1
SMACNA
ASHRAE 0
ASHRAE 1.1
PerformanceMaximum 62°F dew pointRH setpoint (Historic annual average at indoor dry bulb temperature = 70°F, default 50%RH), Class C control (no short term RH range), 25% to 75% seasonal setpoint adjustment, and 62°F dew point maximum.RH setpoint (Historic annual average at indoor dry bulb temperature = 70°F, default 45%RH), Class B controlled range of +/- 10% RH short term, +/- 10% seasonal setoint adjustment, and 62°F dew point maximum.RH setpoint (Historic annual average at indoor dry bulb temperature = 70°F, default 45%RH), Class A controlled range of +/- 5% RH short term, +/- 10% seasonal setoint adjustment (OR +/- 10% RH and NO seasonal setpoint adjustment), and 62°F dew point maximum. Baseline: No
★: No
★★: Yes
★★★: Yes
Baseline: Yes
★: Yes
★★: Yes
★★★: Yes
Show relative humidity control range for each zone and describe method of control when applicable.After occupancy, provide 2 weeks of 15 minute trend history of space relative humidity (when controlled).
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Air Movement
ReferenceASHRAE 55-2010ASHRAE 55-2010ASHRAE 55-2010ASHRAE 55-2010ASHRAE 0
ASHRAE 1.1
SMACNA
ASHRAE 0
ASHRAE 1.1
PerformanceLess than 40 fpm at occupied levelOccupant controlled between 20 and 150 fpmOccupant controlled between 20 and 150 fpmSame as ★★Baseline: No
★: Yes
★★: Yes
★★★: Yes
Baseline: Yes
★: Yes
★★: Yes
★★★: Yes
Describe air speed performance and how it will be achieved by the proposed design.Verify space air speed at occupant level during TAB/Cx.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Pressure
Reference 2009 ASHRAE Handbook – HVAC Fundamentals2009 ASHRAE Handbook – HVAC Fundamentals, Lstiburek (1999), Quirouette (2004)ASHRAE 0
ASHRAE 1.1
SMACNA
ASHRAE 0
ASHRAE 1.1
Coordinate with Building Enclosure Air Tightness metric.
PerformanceActive pressure control by floor to achieve 0.05" w.c. or less positive building pressure when occupied, and when outside dewpoint is higher than 47°F when unoccupied.Maintain building perimeter zones at 0.05" w.c. positive with respect to outdoor; control per exposure per floor when outside dewpoint is higher than 47°F. No design negative pressure spaces at building perimeter.★ and provide envelope cavities at 0.02" w.c. positive with respect to interior occupied space when outside temperature drops below dew point of inside air.Same as ★★, except allow mandatory negative pressure spaces at building perimeter and provide active envelope cavity pressurization at 0.02" w.c. positive with respect to environment with greater dew point.Baseline: Yes
★: Yes
★★: Yes
★★★: Yes
Baseline: Yes
★: Yes
★★: Yes
★★★: Yes
Describe building air pressure performance and how it will be achieved by the proposed design.Prior to occupancy, provide 24 hours of 5-min trend history of building air pressure.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Ventilation
ReferenceASHRAE 62.1-2010ASHRAE 62.1-2010ASHRAE 62.1-2010ASHRAE 62.1-2010ASHRAE 0
ASHRAE 1.1
SMACNA
ASHRAE 0
ASHRAE 1.1
Performance· Standard 62.1 VRP only
· AFMS on VAV systems
· Standard 62.1 VRP only
· LEED EA materials credits
· AFMS on VAV systems
· 20 cfm/person minimum for all occupancies in the breathing zone
· LEED EA materials credits
· AFMS on all systems
· ★★ except:
· 30 cfm/p minimum in offices at breathing zone
Baseline: Yes
★: Yes
★★: Yes
★★★: Yes
Baseline: Yes
P★: Yes
★★: Yes
★★★: Yes
Provide Standard 62.1 VRP calculations for each air handling systemDescribe how minimum ventilation rates will be maintained for all systems.Verify HVAC system minimum ventilation rates during TAB/Cx. Provide 24 hours of 15 minute trend history of each AFMS to verify minimum ventilation control.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Filtration
ReferenceASHRAE 62.1-2010, ASHRAE 52.2-2007ASHRAE 62.1-2010, ASHRAE 52.2-2008ASHRAE 62.1-2010, ASHRAE 52.2-2009ASHRAE 62.1-2010, ASHRAE 52.2-2010ASHRAE 0
ASHRAE 1.1
AABC
NEBB, or TABB
ASHRAE 0
ASHRAE 1.1
Performance· MERV 6 upstream of all cooling coils and other devices with wetted surfaces
· MERV 6 on OA where PM10 limit exceeded
· MERV 11 on OA where PM2.5 limit exceeded
· MERV 8 for all coils
· MERV 11 on OA where PM2.5 limit exceeded
· MERV 8 for all coils
· MERV 13 for outdoor air, no prefilters
· MERV 13 for all supply air units with OA, no prefilters
· MERV 8 for recirculating units with coils
· UVGI at cooling coils
Baseline: Yes
★: Yes
★★: Yes
★★★: Yes
Baseline: Yes
★: Yes
★★: Yes
★★★: Yes
Describe proposed filtration design for all air handling systems.Verify installed filtration during TAB/Cx.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Acoustics
ReferenceASHRAE Handbook - Applications 2007ASHRAE Handbook - Applications 2008ASHRAE Handbook - Applications 2009ASHRAE Handbook - Applications 2010ASTM E336Coordinate with Building Enclosures STC Metric
PerformanceComply with ASHRAE Applications Chapter 48, Table 1Comply with ASHRAE Applications Chapter 48, Table 1Comply with ASHRAE Applications Chapter 48, Table 1 Provide sound maskingComply with ASHRAE Applications Chapter 48, Table 1 Provide sound maskingBaseline: Yes
★: Yes
★★: Yes
★★★: Yes
Baseline: Yes
★: Yes
★★: Yes
★★★: Yes
List design RC level goals for all space types and describe how design will meet these goals.Verify space acoustic sound levels during TAB/Cx.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Operational Efficiency
Equipment Performance90.1-201090.1-201090.1-2009Greater of Tier 2 Energy Star or 189.1-2011YesYesDescribe what efficiency level is proposed for the HVAC equipment.Cx agent to confirm equipment efficiencies during equipment submittal review.
Fan Energy Performance90.1-201090.1-2010 - 5%189.1-2011189.1-2011 - 10%YesProvide fan power limitation calculation per 90.1-2010 Table 6.5.3.1.1.A.Describe how fan energy performance will be less than metric.Cx agent to confirm fan equipment efficiencies during equipment submittal review.
HVAC Energy Performance90.1-201010% Below 90.1-201015% Below 189.1-201130% Below 189.1-2011Provide 90.1-2007 Appendix G energy model demonstrating HVAC annual energy does not exceed project target.Describe HVAC strategies employed in energy model that result in energy target being met.Cx agent to confirm energy model HVAC equipment performance assumptions on design reviews and submittal reviews.
HVAC Energy MeteringNot Required80% of HVAC Energy90% of HVAC Energy100% of HVAC EnergyYesYesProvide energy model results showing that % HVAC energy metering is met.Describe proposed HVAC metering scheme.Calibrate all meters and provide 2 weeks of 15 minute trend history for all HVAC meters.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Maintainability
HVAC Motors>1500 SF/Motor>2000 SF/Motor>3000 SF/Motor>4000 SF/MotorYesProvide the total building square footage divided by the number of HVAC motors.Describe HVAC motor density and locations.Cx agent to confirm during design review.
Air Handler LocationsIndoors/OutdoorsIndoorsIndoorsIndoorsYesDescribe the locations of the the air handling unitsCx agent to confirm during design review.
Equipment and Part ReplacementAccessibleAccessibleEasily AccessibleEasily AccessibleYesDescribe how each piece of equipment can be repaired and replaced.Cx agent to confirm during design review and functional commissioning.
Access DoorsRequiredRequiredRequiredRequiredYesYesDescribe where all access doors have been specified for maintenance access.Cx agent to confirm during design review and functional commissioning.
Motor & Filter Accessibility70% easily accessible without ladders80% easily accessible without ladders90% easily accessible without ladders100% easily accessible without laddersYesShow quantity of filter and motor locations that require ladders to access.Cx agent to confirm during design review and functional commissioning.
MaintenancePeriodicPeriodicPreventiveReliability-CenteredYesDescribe whether a predictive or reliability-based maintenance system has been specified to ease maintenance.Cx agent to confirm during design review and functional commissioning.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Operability
Ease of OperationSpecialized Training for Most SystemsSpecialized Training for Some SystemsSystems are similarSystems are similar and easily operatedYesDescribe what type of training will be required for the building operators.Cx agent to confirm during design review.
Control ComplexityDifficult for average operator to understandDifficult for average operator to understandEasy for average operator to understandEasy for average operator to understandYesProvide a written description of whether the proposed systems are easy or difficult for the average building operator to understand.Cx agent to confirm during design review.
InstrumentationInstrumentation and test ports shall be provided for measuring temperatures and pressures at each piece of HVAC equipmentInstrumentation and test ports shall be provided for measuring temperatures and pressures at each piece of HVAC equipmentInstrumentation and test ports shall be provided for measuring temperatures and pressures at each piece of HVAC equipmentInstrumentation and test ports shall be provided for measuring temperatures and pressures at each piece of HVAC equipmentYesDescribe instrumentation and test port design scheme for ease of operation.Cx agent to confirm during design review.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisDesign Basis of DesignConstruction Verification
  Service Life
Chillers15 Yrs20 Yrs20 Yrs30 YrsYesDescribe construction type and expected service life for each piece of major HVAC equipment.Cx agent to confirm through equipment submittal review.
Cooling Towers15 Yrs20 Yrs25 Yrs35 Yrs
Boilers15 Yrs20 Yrs25 Yrs30 Yrs
Air Handlers20 Yrs25 Yrs30 Yrs40 Yrs
^