The Performance Technical Specifications (PTS) are organized to Level Two of the Uniformat II/Work Breakdown Structure (WBS). Within that structure, the information on particular subsystems is referenced through Level Three and Level Four WBS codes.
The Uniformat II/WBS was selected as the organizational structure for a number of reasons. The reasons included:
- the widespread acceptance of Uniformat II as a systems approach to organizing building elements;
- the systems based organizational structure readily lends itself to performance type specifications; and
- consistency with other Government agencies' (e.g., GSA) organizing structure for projects, estimates, and criteria.
Final Combined Uniformat II / WBS 3/21/07, Revision 3
Unf L1 | Unf L2 | Unf L3 | WBS L4 | Definition | E UOM | M UOM | Quantity Definition | WBS Ref No |
---|---|---|---|---|---|---|---|---|
A | SUBSTRUCTURE | SF | M2 | Footprint area at grade | 01 | |||
This system includes all work below the lowest floor construction (usually slab-on-grade) and the enclosing horizontal and vertical elements required to form a basement, together with the necessary mass excavation and backfill. | ||||||||
A10 | FOUNDATIONS | SF | M2 | Footprint area at grade | ||||
Foundations includes the following Standard Foundations: wall and column foundations; foundation walls up to level of top of slab on grade; pile caps; foundation excavation, backfill, and compaction; footings and bases; perimeter insulation; perimeter drainage; anchor plates; and dewatering. Special Foundations include pile foundations, caissons, underpinning, dewatering, raft foundations, and pressure injected grouting. Slab on grade includes standard slab on grade, structural slab on grade, inclined slab on grade, trenches, pits and bases, and foundation drainage. | ||||||||
A1010 | STANDARD FOUNDATIONS | SF | M2 | Footprint area at grade | 0101 | |||
Continuous footings, spread footings, grade beams, foundation walls, pile caps, and column piers. | ||||||||
A101001 | WALL FOUNDATIONS | LF | M | Length of footings and/or wall foundations | 010101 | |||
Continuous Footings - Assemblies include excavation, hand-shaped bottom, compacted backfill, formwork and keyway, reinforcing steel, concrete and screed finish. | ||||||||
Foundation Walls - Include work items associated with CIP foundation walls, grade beams, or CMU walls. Assemblies include excavation, compacted backfill, perimeter insulation, perimeter drainage, formwork, reinforcing steel, concrete or CMU, and wall finish. | ||||||||
A101002 | COLUMN FOUNDATIONS & PILE CAPS | EA | EA | Number of footings, pile caps and/or piers | 010102 | |||
Spread Footings: Individual or part of continuous pier footings. Assemblies include excavation, backfill and compaction, formwork, reinforcing steel, and concrete and screed finish. If structural steel columns set directly on spread footings, anchor bolts are included in this assembly. | ||||||||
Pile Caps - Assemblies include excavation if required (normally due to installation of piles, the subgrade is at desired level for pile cap), hand-shaped bottom, compacted backfill, formwork, reinforcing steel, and concrete and screed finish. If structural steel columns set directly on spread footings, anchor bolts are included in this assembly. | ||||||||
Column Piers - Assemblies include formwork, reinforcing steel, concrete or CMU, finish, break ties and patch, and set anchor bolts. | ||||||||
A101003 | DEWATERING | SF | M2 | Dewatered area | ||||
Dewatering is the removal of water from excavations. The two principle methods of dewatering are by pump or by a system involving the sinking of a series of well-points around the area and extracting the water by suction pump. Assemblies would include pumps or well points and all associated dewatering materials and equipment. | ||||||||
A101090 | OTHER STANDARD FOUNDATIONS | XX | XX | 01019X | ||||
Standard foundations not described by the assembly categories listed above. | ||||||||
A1020 | SPECIAL FOUNDATIONS | SF | M2 | Footprint area at grade | 0102 | |||
All work associated with special foundations including piles, caissons, and any other special foundation situation. | ||||||||
A102001 | PILE FOUNDATIONS | SF | M2 | Footprint area at grade | 010201 | |||
CIP concrete piles, precast concrete piles, steel pipe piles, steel H-piles, step-tapered steel piles, and treated wood piles. Applicable assemblies would include the material for piles, pile driving, and pile cut-offs if required. | ||||||||
A102002 | CAISSONS | SF | M2 | Footprint area at grade | 010202 | |||
Drilled Caissons - Assemblies include drilled caissons, steel casings if required, reinforcing steel, bell bottom excavation, concrete, and loading and hauling of excavated material. | ||||||||
A102003 | UNDERPINNING | LF | M | Length of underpinning | 010203 | |||
Underpinning is the provision of permanent support for existing buildings by extending their foundations to a new, lower level containing the desired bearing stratum. Assemblies include excavation, backfill, and underpinning materials. | ||||||||
A102004 | DEWATERING | SF | M2 | Dewatered area | 010204 | |||
Dewatering is the removal of water from excavations. The two principle methods of dewatering are by pump or by a system involving the sinking of a series of well-points around the area and extracting the water by suction pump. Assemblies would include pumps or well points and all associated dewatering materials and equipment. | ||||||||
A102005 | RAFT FOUNDATIONS | SF | M2 | Area of raft foundation | 010205 | |||
Raft foundations or spread foundations consist of a solid slab of heavily reinforced concrete covering the entire building footprint area. | ||||||||
A102006 | PRESSURE INJECTED GROUTING | SF | M2 | Footprint area at grade | 010206 | |||
Assemblies provide for injecting cement grout for foundation stabilization. | ||||||||
A102090 | OTHER SPECIAL FOUNDATIONS | XX | XX | 01029X | ||||
These could include cofferdams, soil compaction foundations, and other special foundations. Assemblies would include all material and labor necessary to perform the work for the special foundation condition. | ||||||||
A1030 | SLAB ON GRADE | SF | M2 | Footprint area at grade | 0103 | |||
A slab poured on earth, whether on undisturbed or fill soil. | ||||||||
A103001 | STANDARD SLAB ON GRADE | SF | M2 | Area of slab | 010301 | |||
Standard slab-on-grade is supported by compacted earth or gravel fill. The soil bearing capacity is sufficient to support the slab. Assemblies include fine grade, gravel fill, underslab insulation, edge forms, termite treatment (interior slabs only), vapor barrier, reinforcing, expansion joints, control joints, and finish and curing. Assemblies are based on thickness of slab. | ||||||||
A103002 | STRUCTURAL SLAB ON GRADE | SF | M2 | Area of slab | 010302 | |||
A structural slab-on-grade is not supported by compacted earth or gravel fill. The soil bearing capacity is insufficient to support the slab. A structural slab is generally a minimum of eight inches thick and will be reinforced with reinforcing bars rather than welded wire fabric. Assemblies include fine grade, gravel fill, underslab insulation, edge forms, termite treatment, (interior slabs only), vapor barrier, reinforcing, expansion joints, control joints, and finish and curing. Assemblies are based on thickness of slab. | ||||||||
A103003 | TRENCHES | LF | M | Length of trench | 010304 | |||
Cast-in-place trenches. Assemblies include excavation, hand-shaped bottoms, compacted backfill, formwork, reinforcing steel, concrete, and concrete finish. Examples include trench drains and dust trenches. | ||||||||
A103004 | PITS AND BASES | EA | EA | Number of pits and bases | 010305 | |||
Cast-in-place pits and bases. Assemblies include excavation, hand-shaped bottoms, compacted backfill, formwork, reinforcing steel, concrete, and concrete finish. Examples include elevator pits, dock leveler pits, oil change pits, and bases for equipment. | ||||||||
A103005 | FOUNDATION DRAINAGE | LF | M | Length of foundation | 010306 | |||
Foundation drainage directly associated with draining the foundation. This category does not include storm drainage piping for site. It would include drain pipe or drain tile at foundation or basement for specific purposes of draining foundation or basement. Assemblies would include excavation, hand-shaped bottoms, gravel, compacted backfill, and drain pipe, including accessories. | ||||||||
A103090 | OTHER LOWEST FLOOR CONSTRUCTION | XX | XX | 01039X | ||||
Lowest floor construction not described by the assembly categories listed above. | ||||||||
A20 | BASEMENT CONSTRUCTION | CY | M3 | Volume of excavation | ||||
Work Includes basement excavation, and basement walls. | ||||||||
A2010 | BASEMENT EXCAVATION | CY | M3 | Volume of excavation | 0104 | |||
Excavation work associated with constructing a basement. | ||||||||
A201001 | EXCAVATION FOR BASEMENTS | CY | M3 | Volume of excavation | 010401 | |||
All excavation, stockpiling, and hauling associated with basement excavations are included in this assembly. | ||||||||
A201002 | STRUCTURE BACKFILL & COMPACTION | CY | M3 | Volume of backfill | 010402 | |||
All backfill including hauling in of suitable soils and all necessary compaction is included in this assembly. | ||||||||
A201003 | SHORING | SF | M2 | Shoring contact area | 010403 | |||
This type of shoring is to resist horizontal pressure and not intended to carry vertical loads. Assemblies would include sheet piling or other material and labor used to hold back earth around the perimeter of an excavation. | ||||||||
A201090 | OTHER BASEMENT EXCAVATION | XX | XX | 01049X | ||||
Basement excavation not described by the assembly categories listed above. | ||||||||
A2020 | BASEMENT WALLS | SF | M2 | Area of wall | 0105 | |||
Assembly includes basement perimeter walls that are below grade and below the ground floor level of the building; this also includes elevator pits and other pits. | ||||||||
A202001 | BASEMENT WALL CONSTRUCTION | SF | M2 | Area of wall | 010501 | |||
This includes work items associated with CIP foundation walls or CMU walls and penetrations. Assemblies include formwork, reinforcing steel, concrete or CMU, and wall finish and curing. | ||||||||
A202002 | MOISTURE PROTECTION | SF | M2 | Area of wall moisture protection | 010502 | |||
This assembly would be based on the type and square footage of waterproofing used on the foundation wall. | ||||||||
A202003 | BASEMENT WALL INSULATION | SF | M2 | Area of wall insulation | 010503 | |||
This assembly would be based on the type and square footage of insulation used on the foundation wall. | ||||||||
A202090 | OTHER BASEMENT WALLS | XX | XX | 01059X | ||||
Basement walls not described by the assembly categories listed above. |
Unf L1 | Unf L2 | Unf L3 | WBS L4 | Definition | E UOM | M UOM | Quantity Definition | WBS Ref No |
---|---|---|---|---|---|---|---|---|
B | SHELL | SF | M2 | Area of supported floors | ||||
This system includes all structural slabs, and decks and supports within basements and above grade. Note that the structural work will include both horizontal items (slabs, decks, etc.) and vertical structural components (columns and interior structural walls). Exterior load bearing walls are not included in this system but in System B2010, Exterior Walls. | ||||||||
B10 | SUPERSTRUCTURE | SF | M2 | Area of supported floors | 02 | |||
Work includes floor construction and roof construction. | ||||||||
B1010 | FLOOR CONSTRUCTION | SF | M2 | Area of supported floors | 0201 | |||
This construction can be wood, concrete, CMU, steel frame, etc. | ||||||||
B101001 | STRUCTURAL FRAME | SF | M2 | Area of supported floors | 020101 | |||
The structural frame could consist of structural steel including columns, beams, joists, and all associated items. It could be a concrete frame utilizing concrete or masonry columns and concrete girders and beams. The structural frame could be wood columns with wood beams or wood trusses. The structural frame could be a combination of the above. For example, concrete or masonry columns with structural steel beams and joists. All associated work items should be included in each assembly. Separate assemblies would be used for different types of construction. The unit of measure at the assembly level is the square footage of the supported area. Decks and slabs are not included in this assembly. | ||||||||
B101002 | STRUCTURAL INTERIOR WALLS | SF | M2 | Area of wall | 020102 | |||
Assemblies would be CIP or CMU walls or other structural interior walls. The assemblies would include the labor and material required to perform the construction tasks associated with this type of wall. | ||||||||
B101003 | FLOOR DECKS AND SLABS | SF | M2 | Area of supported floors | 020103 | |||
Slabs above grade should be broken into assemblies according to their particular type of construction (i.e., flat slab, pan slab, precast or pre-stressed slab, four-way slab, slabs on metal or wood decking with concrete fill, etc.). All associated work items should be included in each assembly, such as expansion and contraction joints. | ||||||||
B101004 | INCLINED AND STEPPED FLOORS | SF | M2 | Area of inclined & stepped floors | ||||
This assembly should be broken down according to their particular type of construction (i.e., flat slab, pan slab, precast or pre-stressed slab, four-way slab, slabs on metal or wood decking with concrete fill, etc.). All associated work items should be included in each assembly, such as expansion and contraction joints. | ||||||||
B101005 | BALCONY CONSTRUCTION | SF | M2 | Area of supported balconies | 020104 | |||
Balconies above grade should be broken into assemblies according to their particular type of construction. All associated items including handrails should be included in the assembly. | ||||||||
B101006 | RAMPS | SF | M2 | Area of supported ramps | 020105 | |||
Ramps above grade should be broken into assemblies according to their type of construction. All associated items including handrails should be included in the assembly. | ||||||||
B101007 | FLOOR RACEWAY SYSTEMS | SF | M2 | Gross floor area | 020106 | |||
Under floor or in-slab conduit including conduit and all associated devices. | ||||||||
B101090 | OTHER FLOOR CONSTRUCTION | XX | XX | 02019X | ||||
Any type of special floor construction not included above would fall in this category, such as catwalks, space frames, etc. All associated work items would be included in the assembly. | ||||||||
B1020 | ROOF CONSTRUCTION | SF | M2 | Area of supported roof | 0202 | |||
This construction is similar to floor construction except that is applies to the framework supporting the roof and roof decks. (See also System B30 Roofing.) | ||||||||
B102001 | STRUCTURAL FRAME | SF | M2 | Area of supported roof | 020201 | |||
The structural frame could consist of structural steel including columns, beams, joists, and all associated items. It could be a concrete frame utilizing concrete or masonry columns and concrete girders and beams. The structural frame could be wood columns with wood beams or wood trusses. The structural frame could be a combination of the above. For example, concrete or masonry columns with structural steel beams and joists. All associated work items should be included in each assembly. Separate assemblies would be used for different types of construction. The unit of measure at the assembly level is the square footage of the supported area. Decks and slabs are not included in this assembly. | ||||||||
B102002 | STRUCTURAL INTERIOR WALLS | SF | M2 | Area of walls | 020202 | |||
Assemblies would be CIP or CMU walls or other structural interior walls. The assemblies would include the labor and material required to perform the construction tasks associated with this type of wall. | ||||||||
B102003 | ROOF DECKS AND SLABS | SF | M2 | Area of supported roof | 020203 | |||
Roof decks and slabs should be broken into assemblies according to their particular type of construction (i.e., flat slab, pan slab, precast or pre-stressed slab, four-way slab, slabs on metal or wood decking with concrete fill, etc.). All associated work items should be included in each assembly. | ||||||||
B102004 | CANOPIES | SF | M2 | Area of supported canopies | 020204 | |||
Canopies should be broken into assemblies according to their particular type of construction (i.e., flat slab, pan slab, precast or pre-stressed slab, four-way slab, slabs on metal or wood decking with concrete fill, etc.). All associated work items should be included in each assembly. | ||||||||
B102090 | OTHER ROOF CONSTRUCTION | SF | M2 | Area of supported roof | 02029X | |||
Any type of special roof construction not included above would fall into this category. All associated work items would be included in this assembly. | ||||||||
B20 | EXTERIOR ENCLOSURE | SF | M2 | Area of exterior walls | 03 | |||
This system consists of the exterior facing of the facility, which includes all vertical and horizontal exterior closure such as exterior walls, exterior windows, and exterior doors. This system excludes roofing (See System B30, Roof). Load bearing exterior walls will be included here, and not in System B10, Superstructure. Structural frame elements at exterior such as columns, beams, spandrels, etc., would be included in Superstructure with only the applied exterior finishes (i.e., paint, stucco, etc.) being included here. Finishes to the inside face of walls which are not an integral part of the wall construction will be included in System C30, Interior Finishes. | ||||||||
B2010 | EXTERIOR WALLS | SF | M2 | Area of exterior walls | 0301 | |||
All materials associated with the following construction: exterior load-bearing walls, insulation and vapor barrier, parapets, exterior louvers and screens, sun control devices (exterior), balcony walls and handrails, exterior soffits, screen walls, and exterior coatings. | ||||||||
B201001 | EXTERIOR CLOSURE | SF | M2 | Area of exterior walls | 030101 | |||
Assemblies would include material contained in exterior closure wall, such as masonry with brick veneer. Materials used for interior finishes on exterior walls are not included in this assembly. For example, if the interior side of this masonry wall is sheetrock applied on metal furring strips, the masonry wall is included in this assembly, but the furring strips and sheetrock are categorized as C3010 WALL FINISHES. | ||||||||
B201002 | EXTERIOR WALL BACKUP CONSTRUCTION | SF | M2 | Area of backup walls | ||||
Assemblies used to support structure for the exterior skin and/or provide load-bearing walls for the facility. Materials used for interior finishes on exterior walls are not included in this assembly. For example, if the interior side of this masonry wall is sheetrock applied on metal furring strips, the masonry wall is included in this assembly, but the furring strips and sheetrock are categorized as C3010 WALL FINISHES. | ||||||||
B201003 | INSULATION & VAPOR RETARDER | SF | M2 | Area of insulation | 030102 | |||
Assemblies would include all types of insulation associated with the exterior wall. Rigid, batt and poured insulation should be separated into different assemblies. | ||||||||
B201004 | PARAPETS | LF | M | Length of parapets | 030104 | |||
Assemblies include materials used in association with parapets. Parapets are long walls or railings usually along the edge of a roof or balcony. | ||||||||
B201005 | EXTERIOR LOUVERS & SCREENS | SF | M2 | Area of louvers and screens | 030105 | |||
Assemblies include louvers and screens which are located in exterior walls. The unit of measure at the assembly level is each. | ||||||||
B201006 | BALCONY WALLS & HANDRAILS | LF | M | Length of walls and handrails | 030107 | |||
Assemblies would include materials associated with balcony walls and handrails. These rails are usually guardrails and not associated with stairs. | ||||||||
B201007 | EXTERIOR SOFFITS | SF | M2 | Area of soffits | 030108 | |||
Assemblies would include all associated materials which make up the soffit and supports for the soffit. Typical materials would include wood, aluminum, exterior grade gypboard, stucco, etc. | ||||||||
B201008 | FLASHING | SF | M2 | Area of flashings | ||||
Assemblies include all flashings associated with the exterior walls except for thru-wall flashing. | ||||||||
B201009 | EXTERIOR PAINTING AND SPECIAL COATINGS | SF | M2 | Area of exterior coatings | ||||
Assemblies include paint, stucco, etc. The unit of measure at the assembly level is area of exterior coatings. | ||||||||
B201010 | EXTERIOR JOINT SEALANT | LF | M | Length of sealants | ||||
Exterior application of joint sealants to seal joints and prepare for finish material installation. | ||||||||
B201011 | SUN CONTROL DEVICES | SF | M2 | Area of sun control devices | 030106 | |||
Assemblies include awnings, shades, and solar panels attached to the exterior of the building. A separate assembly should be used for each type of sun control device. | ||||||||
B201012 | SCREEN WALLS | LF | M | Length of screen wall | ||||
Exterior screen walls used for security purposes immediately adjacent to the building such as screen walls at a loading dock. Assemblies would include materials associated with all types of walls. This can also include visual barriers on the roof to screen equipment. Note that perimeter fencing that is typically more than five feet from the building's exterior is included in sitework rather than in this system. | ||||||||
B201090 | OTHER EXTERIOR WALLS | XX | XX | 03019X | ||||
Exterior walls not described by the assembly categories listed above. | ||||||||
B2020 | EXTERIOR WINDOWS | SF | M2 | Area of windows | 0302 | |||
All windows located in exterior walls or exterior skin. | ||||||||
B202001 | WINDOWS | SF | M2 | Area of windows | 030201 | |||
Fixed or operable windows located in exterior walls or exterior skin. Assemblies would include frames, glazing, caulking, finishes and other associated work. | ||||||||
B202002 | STOREFRONTS | SF | M2 | Area of storefronts | 030202 | |||
Fixed storefronts including associated doors in exterior walls or exterior skin. Assemblies would include integral storefront doors, frames, glazing, caulking, finishes, and other associated work. | ||||||||
B202003 | CURTAIN WALLS | SF | M2 | Area of curtain walls | 030203 | |||
This applies to glass curtain walls and spandrel glass in exterior walls or exterior skin. Assemblies would include integral curtainwall doors, frames, glazing, caulking, finishes, and other associated work. | ||||||||
B202004 | EXTERIOR GLAZING | SF | M2 | Area of Glazing | ||||
B202090 | OTHER EXTERIOR WINDOWS | XX | XX | 03029X | ||||
Exterior windows not described by the assembly categories listed above. | ||||||||
B2030 | EXTERIOR DOORS | EA | EA | Number of doors | 0303 | |||
All doors located in exterior walls or exterior skin. | ||||||||
B203001 | SOLID DOORS | EA | EA | Number of doors | 030302 | |||
Assemblies include all exterior solid doors, hollow metal or wood with frames. Solid doors may include glazing lites in doors. Door hardware is located in B203008 EXTERIOR DOOR HARDWARE. | ||||||||
B203002 | GLAZED DOORS | EA | EA | Number of doors | 030301 | |||
Assemblies include all full glazed exterior doors with glass, frames not included in storefront and curtainwalls. These doors can be made of storefront materials but are not part of a curtainwall or storefront. Door hardware is located in B203008 EXTERIOR DOOR HARDWARE. | ||||||||
B203003 | REVOLVING DOORS | EA | EA | Number of doors | 030303 | |||
Assemblies include all revolving doors at exterior of the facility. | ||||||||
B203004 | OVERHEAD AND ROLL-UP DOORS | SF | M2 | Area of doors | 030401 | |||
Overhead and roll-up doors installed in exterior walls or exterior skin. Assemblies include frames, hardware, hoisting devices, and finish and other associated work. The unit of measure at the assembly level is each door. | ||||||||
B203005 | HANGAR DOORS | SF | M2 | Area of doors | 030402 | |||
Large aircraft doors used on medium and high bay hangars. Assemblies would include frames, hardware, hoisting devices, and finish and other associated work. | ||||||||
B203006 | BLAST RESISTANT DOORS | SF | M2 | Area of doors | 030403 | |||
Special exterior doors used for blast resistance. Assemblies would include frames, hardware, hoisting devices, and finish and other associated work. | ||||||||
B203007 | GATES | SF | M2 | Area of doors | 030404 | |||
Any special gate type used in the exterior wall or exterior skin of the building. Assemblies would include frames, hardware, hoisting devices, and finish and other associated work. The unit of measure at the assembly level is each gate. | ||||||||
B203008 | EXTERIOR DOOR HARDWARE | EA | EA | Number of doors | ||||
Exterior door hardware includes items such as closers, hinges, locksets, panic hardware, etc. | ||||||||
B203090 | OTHER EXTERIOR SPECIALTY DOORS | XX | XX | 03049X | ||||
Any special type door used in the exterior wall or exterior skin of the building. Assemblies would include frames, hardware, hoisting devices, and finish and other associated work. The unit measure at the assembly level is each door, or area of special doors, i.e., hangar doors. | ||||||||
B203091 | OTHER EXTERIOR PERSONNEL DOORS | XX | XX | 03039X | ||||
Exterior personnel doors not described by the assembly categories listed above. | ||||||||
B30 | ROOFING | SF | M2 | Gross area of roof | 04 | |||
This System includes all waterproof roof coverings and insulation, expansion joints, together with skylights, hatches, ventilators, and all required trim. In addition to roof coverings, the system includes all waterproof membranes and traffic toppings over below grade enclosed areas, balconies, and the like. | ||||||||
B3010 | ROOF COVERINGS | SF | M2 | Gross area of roof | 0401 | |||
This System includes all waterproof roof coverings and insulation, expansion joints, together with skylights, hatches, ventilators, and all required trim. In addition to roof coverings, the system includes all waterproof membranes and traffic toppings over below grade enclosed areas, balconies, and the like. | ||||||||
B301001 | STEEP SLOPE ROOF SYSTEMS | SF | M2 | Area of roof covering | 040101 | |||
Assemblies include roof coverings such as shingle, wood shake, structural standing seam, metal roofing, etc. | ||||||||
B301002 | LOW SLOPE ROOF SYSTEMS | SF | M2 | Area of topping or membrane | ||||
Assemblies include roof coverings such as built-up, elastomeric, modified bitumen, etc. Also, walkways and work areas (used to gain access to rooftop equipment) will be included here. | ||||||||
B301003 | ROOF INSULATION & FILL | SF | M2 | Area of insulation | 040103 | |||
Assemblies include all types of insulation associated with the roof area. | ||||||||
B301004 | FLASHINGS & TRIM | SF | M2 | Area of flashings | 040104 | |||
Assemblies include all flashings associated with the roof, i.e., eave flashing, gable flashing, etc. | ||||||||
B301005 | GUTTERS & DOWNSPOUTS | LF | M | Length of gutters and downspouts | 040106 | |||
Assemblies include all gutters, downspouts, and associated work including splash blocks. | ||||||||
B301006 | ROOF OPENINGS AND SUPPORTS | SF | M2 | Area of openings | 040105 | |||
All roof penetrations including roof hatches, sky lights, area glazing, gravity roof ventilators, smoke vents, etc. | ||||||||
B301090 | OTHER ROOFING | XX | XX | 04019X | ||||
Roofing not described by the assembly categories listed above. |
Unf L1 | Unf L2 | Unf L3 | WBS L4 | Definition | E UOM | M UOM | Quantity Definition | WBS Ref No |
---|---|---|---|---|---|---|---|---|
C | INTERIOR | SF | M2 | Gross floor area | 05 | |||
Construction which takes place inside the exterior wall or exterior closure. The system does not include interior structural walls, which are included in B1010 FLOOR CONSTRUCTION and B1020 ROOF CONSTRUCTION. | ||||||||
C10 | INTERIOR CONSTRUCTION | SF | M2 | Gross floor area | ||||
This assembly includes partitions, interior doors, and specialties. | ||||||||
C1010 | PARTITIONS | SF | M2 | Area of partitions | 0501 | |||
Includes all interior partitions. | ||||||||
C101001 | FIXED PARTITIONS | SF | M2 | Area of fixed partition walls | 050101 | |||
Interior fixed partitions include metal or wood studs, sheetrock, masonry, and concrete walls. | ||||||||
C101002 | DEMOUNTABLE PARTITIONS | SF | M2 | Area of demountable partition walls | 050102 | |||
Assemblies would include all demountable partitions and associated work including tracks and anchoring systems. | ||||||||
C101003 | RETRACTABLE PARTITIONS | SF | M2 | Area of retractable partition walls | 050103 | |||
Assemblies would include all retractable or folding partitions and associated work including tracks and anchoring systems. | ||||||||
C101004 | INTERIOR GUARDRAILS & SCREENS | LF | M | Length of balustrades and screens | 050104 | |||
Assemblies include balustrades (balcony handrails and the row screen of posts that support them) and screens and associated work including tracks and anchoring systems. These balustrades/guardrails are related to interior balconies and are not associated with stairs. | ||||||||
C101005 | INTERIOR WINDOWS | SF | M2 | Area of windows | 050105 | |||
Fixed or operable windows. Assemblies would include frames, glazing, caulking and other associated work. | ||||||||
C101006 | GLAZED PARTITIONS & STOREFRONTS | SF | M2 | Area of partitions and storefronts | 050106 | |||
Fixed interior glazed partitions including interior storefronts with doors. Assemblies include frames, glazing, caulking, and other associated work. | ||||||||
C101007 | INTERIOR GLAZING | SF | M2 | Area of interior glazing | ||||
C101008 | INTERIOR JOINT SEALANT | LF | M | Length of sealants | ||||
Interior application of sealants to seal joints and prepare for finish material installation. The application shall include partitions, doors and fitting. | ||||||||
C101090 | OTHER PARTITIONS | XX | XX | 05019X | ||||
Interior partitions not described by the assembly categories listed above. | ||||||||
C1020 | INTERIOR DOORS | LEF | LEF | Number of leaves | 0502 | |||
All interior doors. | ||||||||
C102001 | STANDARD INTERIOR DOORS | LEF | LEF | Number of leaves | 050201 | |||
Assemblies include all standard interior wood or hollow metal doors with frames, finish, etc. Standard interior door may include vision lites. Interior door hardware is located in C102007 INTERIOR DOOR HARDWARE. | ||||||||
C102002 | GLAZED INTERIOR DOORS | LEF | LEF | Number of leaves | 050202 | |||
Assemblies include all glazed interior doors with glass, frames, finish, including storefront, etc. Interior door hardware is located in C102007 INTERIOR DOOR HARDWARE. | ||||||||
C102003 | FIRE DOORS | LEF | LEF | Number of leaves | 050203 | |||
Assemblies include all interior fire doors, including all necessary frames, and sensing devices integral with the door. Interior door hardware is located in C102007 INTERIOR DOOR HARDWARE. | ||||||||
C102004 | SLIDING & FOLDING DOORS | SF | M2 | Area of sliding or folding door | 050204 | |||
Assemblies include all sliding and folding doors with frames, hardware, locking devices, tracks, and supporting systems. The unit of measure at the assembly level is each. | ||||||||
C102005 | INTERIOR OVERHEAD DOORS | SF | M2 | Area of doors | 050301 | |||
Overhead doors installed in the interior of a facility. Assemblies include frames, hardware, hoisting devices, and finish and other associated work. The unit of measure at the assembly level is each door. | ||||||||
C102006 | INTERIOR GATES | SF | M2 | Area of gates | 050302 | |||
Any special type gate installed in the interior of a facility. Assemblies include frames, hardware, hoisting devices, and finish and other associated work. The unit measure at the assembly level is each gate. | ||||||||
C102007 | INTERIOR DOOR HARDWARE | EA | EA | Number of doors | ||||
Interior door hardware includes items such as closers, hinges, locksets, panic hardware, etc. | ||||||||
C102090 | OTHER INTERIOR SPECIALTY DOORS | XX | XX | 05039X | ||||
Any special type door installed in the interior of a facility. Assemblies include frames, hardware, hoisting devices, and finish and other associated work. The unit measure at the assembly level is each gate. | ||||||||
C102091 | OTHER INTERIOR PERSONNEL DOORS | XX | XX | 05029X | ||||
Interior personnel doors not described by the assembly categories listed above. | ||||||||
C1030 | SPECIALTIES | SF | M2 | Gross floor area | 0504 | |||
Most commonly used specialty items. | ||||||||
C103001 | COMPARTMENTS, CUBICLES & TOILET PARTITIONS | EA | EA | Number of compartments, cubicles, or toilet partitions | 050401 | |||
Assemblies include individual compartments, cubicles, toilet partitions, and urinal screens. | ||||||||
C103002 | TOILET & BATH ACCESSORIES | EA | EA | Number of accessories | 050402 | |||
Toilet and bath accessories. For example, soap dispensers, toilet paper holder, towel dispensers, grab bars, bathroom mirrors, etc. | ||||||||
C103003 | MARKER BOARDS & TACK BOARDS | EA | EA | Each Board | 050403 | |||
Assemblies include all marker boards, tackboards, and fastening devices. The unit of measure at the assembly level is each. | ||||||||
C103004 | IDENTIFYING DEVICES | EA | EA | Number of identifying devices | 050404 | |||
Assemblies include all signs, plaques, traffic markers, etc. | ||||||||
C103005 | LOCKERS | EA | EA | Number of lockers | 050405 | |||
Assemblies include all types of lockers, either wood or metal, single or double tier. Special bases used for lockers would be included in this assembly. | ||||||||
C103006 | SHELVING | LF | M | Length of shelving | 050406 | |||
Assemblies include all types of shelving with brackets and all supporting materials and finish, if required. | ||||||||
C103007 | FIRE EXTINGUISHER CABINETS | EA | EA | Number of fire extinguisher cabinets | 050407 | |||
This assembly would include all types and sizes of fire extinguisher cabinets. Fire extinguishers are not included in this assembly; they are included in D40. | ||||||||
C103008 | COUNTERS | LF | M | Length of counters | 050501 | |||
Assemblies include all counters and countertops with all necessary brackets and supporting materials and finish, if required. | ||||||||
C103009 | CABINETS | LF | M | Length of cabinets | 050502 | |||
This assembly includes all cabinetry and millwork items with associated accessories and anchoring devices. Cabinet finishes are included in this assembly. Metal cabinets and special use cabinetry (medical, dental, libraries, etc.) are included in C103010 CASEWORK. | ||||||||
C103010 | CASEWORK | LF | M | Length of casework | ||||
Assemblies would include built-in premanufactured cabinetry for specialized functions such as labs, libraries, medical and dental facilities. | ||||||||
C103011 | CLOSETS | LF | M | Length of closets | 050503 | |||
This assembly includes all built-in closets with all associated work and finishes. These closets are millwork items or prefabricated coat closets for schools and dormitories. | ||||||||
C103012 | FIRESTOPPING PENETRATIONS | EA | EA | Each Penetration | ||||
Assembly includes sleeve, caulking, and flashing. | ||||||||
C103013 | SPRAYED FIRE-RESISTIVE MATERIALS | SF | M2 | Area of coverage | ||||
Sprayed Fire-Resistive Materials includes materials that are applied primarily to a building's framework (columns, beams, bracing, metal decking) to prevent structural failure. | ||||||||
C103014 | ENTRANCE FLOOR GRILLES AND MATS | SF | M2 | Area of grilles/mats | ||||
Assemblies include floor grilles and mats installed in a fixed arrangement at a building entrance. | ||||||||
C103015 | ORNAMENTAL METALWORK | EA | EA | Number of metalwork items | ||||
Building components made from ornamental metals. Ornamental stair handrails are included in B1010 EXTERIOR STAIRS and C20 STAIRS. | ||||||||
C103090 | OTHER INTERIOR SPECIALTIES | EA | EA | Number of specialty items | 05049X | |||
Interior specialties not described by the assembly categories listed above. | ||||||||
C20 | STAIRS | FLT | FLT | Number of flights | ||||
Work includes all stair construction. | ||||||||
C2010 | STAIR CONSTRUCTION | FLT | FLT | Number of flights | 0203 | |||
All work items located within the building footprint. A flight of stairs is considered to be all the treads and risers with landings required to travel from one floor to the next. | ||||||||
C201001 | INTERIOR AND EXTERIOR STAIRS | FLT | FLT | Number of flights | 020301 | |||
All stair work items associated with non-fire escape stairs. The stairs can be either interior stairs or stairs exposed to the weather. Exterior stairs are exposed to the outside and do not typically require HVAC. A flight of stairs is considered to be all the treads and risers with landings required to travel from one floor to the next. | ||||||||
C201002 | FIRE ESCAPE STAIRS | FLT | FLT | Number of flights | ||||
Assemblies include exterior stairs which are used for emergency egress. These stairs are exposed to the weather. Handrails, finishes and associated work items are included in this assembly. | ||||||||
C201090 | STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES | XX | XX | 02039X | ||||
Stair handrails, guardrails, and cast-in-place nosings for interior and exterior stairs. | ||||||||
C30 | INTERIOR FINISHES | SF | M2 | Area of finishing | 06 | |||
Includes wall finishes, floor finishes, and ceiling finishes. | ||||||||
C3010 | WALL FINISHES | SF | M2 | Area of finished walls | 0601 | |||
Finishes which are applied to interior wall surfaces. For coatings, refer to C3040. | ||||||||
C301001 | CONCRETE WALL FINISHES | SF | M2 | Area of finished walls | 060101 | |||
This assembly would include a concrete finish applied directly to an interior wall surface. This assembly does not include items that directly apply to wall finishes covered elsewhere in this subsystem. | ||||||||
C301002 | PLASTER WALL FINISHES | SF | M2 | Area of finished walls | 060102 | |||
This assembly includes plaster or stucco applied directly to an interior wall surface. Lath and associated work would be included in this assembly. This assembly does not include items that directly apply to wall finishes covered elsewhere in this subsystem. | ||||||||
C301003 | GYPSUM WALLBOARD FINISHES | SF | M2 | Area of finished walls | 060103 | |||
This assembly includes gypsum wallboard applied directly to an interior wall surface. Furring strips or channels are included in this assembly. This assembly also includes taping, sanding, finishing, and sheetrock accessories. This assembly does not include items that directly apply to wall finishes covered elsewhere in this subsystem. | ||||||||
C301004 | TILE & TERRAZZO WALL FINISHES | SF | M2 | Area of finished walls | 060104 | |||
This assembly includes tile and terrazzo applied directly to an interior wall surface. Each type of tile would be a separate assembly. | ||||||||
C301005 | WALL COVERINGS | SF | M2 | Area of wall coverings | 060106 | |||
This assembly includes wall coverings and protective strips applied directly to an interior wall surface. | ||||||||
C301006 | ACOUSTICAL PANELS ADHERED TO WALLS | SF | M2 | Area of acoustical tiles and panels | 060107 | |||
This assembly includes acoustical tiles and panels with associated work applied directly to an interior wall surface. | ||||||||
C301090 | OTHER WALL FINISHES | XX | XX | 06019X | ||||
Assemblies include finishes to wall types not included above. These include, but are not limited to, different types of shielding and the work and materials associated with each. | ||||||||
C3020 | FLOOR FINISHES | SF | M2 | Area of finished floors | 0602 | |||
All flooring and floor finishes applied to interior floors. For coatings refer to C3040. | ||||||||
C302001 | TILE FLOOR FINISHES | SF | M2 | Area of tile floors | 060201 | |||
Assemblies include ceramic, quarry, and other non-resilient tile floors. | ||||||||
C302002 | TERRAZZO FLOOR FINISHES | SF | M2 | Area of terrazzo floors | 060202 | |||
Assemblies include terrazzo floors. | ||||||||
C302003 | WOOD FLOORING | SF | M2 | Area of wood floors | 060203 | |||
Assemblies include wood floors. | ||||||||
C302004 | RESILIENT FLOOR FINISHES | SF | M2 | Area of resilient floors | 060204 | |||
Assemblies include resilient floors. | ||||||||
C302005 | CARPETING | SF | M2 | Area of carpeting | 060205 | |||
C302006 | MASONRY & STONE FLOORING | SF | M2 | Area of masonry or stone flooring | 060206 | |||
Assemblies include masonry, concrete pavers, and stone flooring. | ||||||||
C302007 | WALL BASE FINISHES | LF | M | Length of wall base | ||||
Assemblies include wall base, consisting of various materials such as vinyl, ceramic tile, etc. | ||||||||
C302008 | STAIR FINISHES | SF | M2 | Area of coverage | ||||
Includes field-applied finish materials (other than paint) to surfaces of stairs including treads, risers and landings. | ||||||||
C302009 | FLOOR TOPPINGS AND TRAFFIC MEMBRANES | SF | M2 | Area of coverage | ||||
Assemblies include floor toppings and membrane systems. | ||||||||
C302010 | HARDENERS AND SEALERS | SF | M2 | Area of coverage | ||||
Assemblies include floor hardeners and sealers, typically applied on concrete floors. | ||||||||
C302011 | RAISED ACCESS FLOORING | SF | M2 | Area of special flooring | ||||
Assemblies include all types of raised flooring, pedestal access floors and other types of access flooring. | ||||||||
C302090 | OTHER FLOORING & FLOOR FINISHES | XX | XX | 06029X | ||||
Assemblies include floor finishes not described by the assembly categories listed above, such as conductive, armored, etc. | ||||||||
C3030 | CEILING FINISHES | SF | M2 | Area of ceilings | 0603 | |||
All ceilings and ceiling finishes applied to interiors. For coatings, refer to C3040. | ||||||||
C303001 | ACOUSTICAL CEILING TILES & PANELS | SF | M2 | Area of acoustical ceilings | 060304 | |||
Assemblies include acoustical ceiling tiles and panels. The suspension system, if required, is in Assembly Category C303005. This assembly does not include items that directly apply to ceiling finishes covered elsewhere in this subsystem. | ||||||||
C303002 | GYPSUM WALLBOARD CEILING FINISHES | SF | M2 | Area of gypsum ceilings | 060303 | |||
Assemblies include gypsum wallboard applied to interior ceilings. Furring strips or channels are included in this assembly if they are applied directly to the ceiling surface. If the gypsum board is applied to a suspended ceiling system, the suspended system would be in Assembly Category C303005. This assembly does not include items that directly apply to ceiling finishes covered elsewhere in this subsystem. | ||||||||
C303003 | PLASTER CEILING FINISHES | SF | M2 | Area of plaster ceiling finish | 060302 | |||
Assemblies include plaster or stucco finishes applied to interior ceilings. Lath and associated work would apply to this assembly. This assembly does not include items that directly apply to ceiling finishes covered elsewhere in this subsystem. | ||||||||
C303004 | WOOD CEILINGS | SF | M2 | Area of wood ceilings | 060305 | |||
Assemblies include wood ceilings. Different types of wood ceilings should be separated into different assemblies. If the wood ceiling is applied to a suspended ceiling system, the suspended system would be in Assembly Category C303005. This assembly does not include items that directly apply to ceiling finishes covered elsewhere in this subsystem. | ||||||||
C303005 | SUSPENSIONS SYSTEMS | SF | M2 | Area of suspension system | 060307 | |||
This assembly includes any suspension system which is suspended or hung from the structure for the purpose of fastening a ceiling. | ||||||||
C303006 | METAL STRIP CEILINGS | SF | M2 | Area of metal ceiling | 060308 | |||
Assemblies include all metal strip materials applied to ceilings. | ||||||||
C303090 | OTHER CEILING & CEILING FINISHES | XX | XX | 06039X | ||||
Special ceilings and ceiling finishes not described by the assembly categories listed above. | ||||||||
C3040 | INTERIOR COATINGS AND SPECIAL FINISHES | SF | M2 | Area of interior coatings | ||||
This assembly includes surface preparation and application of coatings to interior surfaces. | ||||||||
C304001 | GENERAL REQUIREMENTS | SF | M2 | Area of coatings and finishes | 0 | |||
C304002 | CONCRETE FINISHES | SF | M2 | Area of concrete finishes | 0 | |||
C304003 | CONCRETE MASONRY FINISHES | SF | M2 | Area of concrete masonry finishes | 0 | |||
C304004 | METAL FINISHES | SF | M2 | Area of metal finishes | 0 | |||
C304005 | INTERIOR WOOD FINISHES | SF | M2 | Area of wood finishes | 0 | |||
C304006 | GYPSUM WALLBOARD FINISHES | SF | M2 | Area of gypsum wallboard coatings | 0 | |||
C304007 | SPECIAL COATINGS ON WALLS | SF | M2 | Area of special wall coatings | 0 |
Unf L1 | Unf L2 | Unf L3 | WBS L4 | Definition | E UOM | M UOM | Quantity Definition | WBS Ref No |
---|---|---|---|---|---|---|---|---|
D | SERVICES | EA | EA | |||||
Includes all methods of conveying, plumbing, HVAC, fire protection, and electrical. | ||||||||
D10 | CONVEYING | STY | STY | Number of stories | 07 | |||
This system includes elevators, escalators, pneumatic tube systems, conveyors, chutes, etc. Foundations for these systems are included in System A, Substructure. | ||||||||
D1010 | ELEVATORS AND LIFTS | STP | STP | Number of stops | 0701 | |||
Includes passenger elevators and freight elevators. | ||||||||
D101001 | GENERAL CONSTRUCTION ITEMS | EA | EA | Number of items | 070101 | |||
Includes construction work, other than conveying system work, which must be performed in conjunction with this type of work to complete the system. | ||||||||
D101002 | PASSENGER ELEVATORS | STP | STP | Number of stops | 070102 | |||
The unit measure at the assembly level is each stop. | ||||||||
D101003 | FREIGHT ELEVATORS | STP | STP | Number of stops | 070103 | |||
The unit measure at the assembly level is each stop. | ||||||||
D101004 | WHEELCHAIR LIFT | EA | EA | Number of lifts | ||||
Premanufactured lift to gain wheelchair access. | ||||||||
D101005 | DUMBWAITERS | STP | STP | Number of stops | ||||
The unit measure of the assembly is each stop. | ||||||||
D101090 | OTHER VERTICAL TRANSPORTATION EQUIPMENT | XX | XX | 07019X | ||||
This includes elevators not described by the assembly categories listed above, such as people lifts. | ||||||||
D1020 | WEIGHT HANDLING EQUIPMENT | EA | EA | Number of items | 0 | |||
D102001 | BASIC REQUIREMENTS OF CRANES AND MONORAILS | EA | EA | Number of items | 0 | |||
D102002 | OVERHEAD CRANES | EA | EA | Number of items | 0 | |||
D102003 | MONORAILS | EA | EA | Number of items | 0 | |||
D1030 | ESCALATORS AND MOVING WALKS | LF | M | Length of stairs or walks | 0702 | |||
D103001 | ESCALATORS | LF | M | Length of stairs | 070201 | |||
D103002 | MOVING WALKS | LF | M | Length of walks | 070202 | |||
D103090 | OTHER MOVING STAIRS & WALKS | XX | XX | 07029X | ||||
Moving stairs or walks not described by the assembly categories listed above. | ||||||||
D1090 | OTHER CONVEYING SYSTEMS | EA | EA | Number of systems | ||||
Other conveying systems includes pneumatic tube systems, conveyor belts, chutes, and transportation systems. | ||||||||
D109001 | PNEUMATIC TUBE SYSTEMS | EA | EA | Number of systems | 070306 | |||
D109002 | CONVEYORS | EA | EA | Number of material handling systems | ||||
D109003 | LINEN, TRASH, AND MAIL CHUTES | LF | M | Length of chute | ||||
D109004 | TURNTABLES | EA | EA | Number of turntables | ||||
D109005 | OPERABLE SCAFFOLDING | SF | M2 | Area of scaffolding | ||||
D109006 | TRANSPORTATION SYSTEMS | EA | EA | Number of systems | ||||
This assembly includes baggage handling and aircraft loading systems. | ||||||||
D109090 | OTHER MATERIAL HANDLING SYSTEMS | XX | XX | 07039X | ||||
Material or handling systems not described by the assembly categories listed above. | ||||||||
D20 | PLUMBING | EA | EA | Number of fixtures | 08 | |||
The plumbing system's primary function is the transfer of liquids and gases. This system includes all water supply and waste items within the building. | ||||||||
D2010 | PLUMBING FIXTURES | EA | EA | Number of fixtures | 0801 | |||
All terminal devices on the domestic plumbing system which have water supplied to the fixture. Hot water heaters, hose bibbs, and special equipment are not counted as a fixture. | ||||||||
D201001 | WATERCLOSETS | EA | EA | Number of fixtures | 080101 | |||
D201002 | URINALS | EA | EA | Number of fixtures | 080102 | |||
D201003 | LAVATORIES | EA | EA | Number of fixtures | 080103 | |||
D201004 | SINKS | EA | EA | Number of fixtures | 080104 | |||
D201005 | SHOWERS/TUBS | EA | EA | Number of fixtures | 080105 | |||
D201006 | DRINKING FOUNTAINS & COOLERS | EA | EA | Number of fixtures | 080106 | |||
D201007 | BIDETS | EA | EA | Number of fixtures | ||||
D201090 | EMERGENCY FIXTURES | XX | XX | |||||
Emergency fixtures not described by the assembly categories listed above. | ||||||||
D2020 | DOMESTIC WATER DISTRIBUTION | EA | EA | Number of fixtures | 0802 | |||
This system provides for human health and comfort. The water supply needed is determined by the number of fixtures attached. Hot water heaters, hose bibbs, and special equipment are not counted as a fixture. | ||||||||
D202001 | PIPES & FITTINGS | EA | EA | Number of fixtures | 080201 | |||
Assemblies include all pipe, fittings, and associated work with regard to domestic water supply. The unit of measure at the assembly level is number of fixtures. | ||||||||
D202002 | VALVES & HYDRANTS | EA | EA | Number of valves and hydrants | 080202 | |||
Assemblies include all valves and hydrants. Hose bibbs are included in this assembly. The unit of measure at the assembly level is number of valves and hydrants. | ||||||||
D202003 | DOMESTIC WATER EQUIPMENT | EA | EA | Number of fixtures | 080501 | |||
This assembly includes equipment associated with the domestic water supply, including fittings, and specialties required for hook-up. Assemblies include hot water heaters, water treatment plant, i.e., water softeners, filters, distillers, etc.; pumps directly associated with domestic water supply; and tanks for the potable hot or cold water system. The unit of measure at the assembly level is pieces of equipment. | ||||||||
D202004 | INSULATION & IDENTIFICATION | EA | EA | Number of fixtures | 080204 | |||
Assemblies include insulation used in association with domestic water supply. The unit of measure at the assembly level is number of fixtures. | ||||||||
D202005 | SPECIALTIES | EA | EA | Pieces of equipment | 080205 | |||
Any other special items associated with domestic water supply. All associated work items, including pipes, fittings, valves, insulation, and hook-up should be included in this assembly. The unit of measure at the assembly level is pieces of special equipment. | ||||||||
D202090 | OTHER DOMESTIC WATER SUPPLY | XX | XX | 08029X | ||||
Domestic water supply not described by the assembly categories listed above. | ||||||||
D2030 | SANITARY WASTE | EA | EA | Number of fixtures | 0803 | |||
This system provides for human health and comfort. Fixtures include all terminal devices which have a water supply (except water supply equipment and specialties), and also devices that transfer fluids into the sanitary waste system that do not have a water supply. Floor drains (not drain hubs) are included as a sanitary waste fixture. | ||||||||
D203001 | WASTE PIPE & FITTINGS | EA | EA | Number of fixtures | 080302 | |||
Assemblies include all pipe, fittings, and associated work with regard to sanitary waste pipe and fittings. The unit of measure at the assembly level is number of fixtures. | ||||||||
D203002 | VENT PIPE & FITTINGS | EA | EA | Number of fixtures | 080302 | |||
Assemblies include all pipe, fittings, and associated work with regard to sanitary vent pipe and fittings. The unit of measure at the assembly level is number of fixtures. | ||||||||
D203003 | FLOOR DRAINS | EA | EA | Number of floor drains | 080303 | |||
Assemblies include all floor drains. Hub drains are considered to be pipe and are not included in this category. The unit of measure at the assembly level is number of drains. | ||||||||
D203004 | SANITARY AND VENT EQUIPMENT | EA | EA | Number of fixtures | 080502 | |||
This is equipment associated with the sanitary waste system, including fittings and specialties required for hook-up. Assemblies include waste treatment equipment, i.e., sluice gates, incinerators, etc.; pumps for sewage injection; and holding tanks for the domestic water system. The unit of measure at the assembly level is pieces of equipment. | ||||||||
D203005 | INSULATION & IDENTIFICATION | EA | EA | Number of fixtures | 080304 | |||
Assemblies include insulation used in association with sanitary waste and vent system. The unit of measure at the assembly level is number of fixtures. | ||||||||
D203090 | OTHER SANITARY WASTE | XX | XX | 08039X | ||||
Sanitary waste and vent not described by the assembly categories listed above. | ||||||||
D2040 | RAIN WATER DRAINAGE | SF | M2 | Area of roof | 0804 | |||
Roof drainage system. Gutter and downspouts are not included in this subsystem. | ||||||||
D204001 | PIPE & FITTINGS | LF | M | Length of pipe | 080401 | |||
Assemblies include pipe and fittings from the roof drains to the discharge points, including supports and other associated work. | ||||||||
D204002 | ROOF DRAINS | EA | EA | Number of roof drains | 080402 | |||
Assemblies include roof drains. The unit of measure at the assembly level is number of drains. | ||||||||
D204003 | RAINWATER DRAINAGE EQUIPMENT | EA | EA | Pieces of equipment | 080503 | |||
This is equipment associated with the rain water drainage, including fittings and specialties required for hook-up. Assemblies include pumps and other associated items for drainage of rain water. | ||||||||
D204004 | INSULATION & IDENTIFICATION | LF | M | Length of pipe insulation | 080403 | |||
Assemblies include insulation used in association with rain water drainage system. | ||||||||
D204090 | OTHER RAIN WATER DRAINAGE SYSTEM | XX | XX | 08049X | ||||
Rain water drainage system not described by the assembly categories listed above. | ||||||||
D2090 | OTHER PLUMBING SYSTEMS | EA | EA | Number of special fixtures, etc. | 0806 | |||
This subsystem includes all special plumbing systems which are not included in D2010 through D2040. | ||||||||
D209001 | SPECIAL PIPING SYSTEMS | EA | EA | Number of special fixtures, interceptors, etc. | 080601 | |||
Assemblies include all special pipe and fittings, excluding acid waste pipe and work with regard to special pipe. Medical gas and vacuum fittings, and associated systems piping are included in this category. The unit of measure at the assembly level is the number of special fixtures, interceptors, outlets, or systems. | ||||||||
D209002 | ACID WASTE SYSTEMS | EA | EA | Number of special fixtures, interceptors, etc. | 080602 | |||
Assemblies include all pipe, fittings, special acid waste equipment, and other associated work items with regard to acid waste systems. The unit of measure at the assembly level is the number of special fixtures, interceptors, outlets, or systems. | ||||||||
D209003 | INTERCEPTORS | EA | EA | Number of interceptors | 080603 | |||
Assemblies include all interceptors. The unit of measure at the assembly level is number of interceptors. | ||||||||
D209004 | POOL PIPING AND EQUIPMENT | GPM | M3/S | Gallons per minute | 080604 | |||
Assemblies include pumps and associated equipment with pools, including specialties required for hook-up. The unit of measure at the assembly level is each. | ||||||||
D209005 | COMPRESSED AIR SYSTEM (NON-BREATHING) | PSI | KGM2 | Pounds per square inch | ||||
D209090 | OTHER SPECIAL PLUMBING SYSTEMS | XX | XX | 08069X | ||||
This system includes special plumbing systems not described by the assembly categories listed above, such as fountain piping systems and devices. | ||||||||
D30 | HVAC | MBH | KW | Total MBH capacity | 09 | |||
This system includes all equipment, distribution systems, controls, and energy supply systems required by the heating, ventilating, and air conditioning system. | ||||||||
D3010 | ENERGY SUPPLY | MBH | KW | Total power of heating system | 0901 | |||
The energy input to the facility (other than electrical) in the form of fuels or hot and cold water distributed from a central base facility. Energy received from wind or solar power is included in this subsystem. | ||||||||
D301001 | OIL SUPPLY SYSTEM | MBH | KW | Calories per gallon | 090101 | |||
Assemblies include storage equipment, transfer equipment, and distribution piping. The unit of measure at the assembly level is each system. | ||||||||
D301002 | GAS SUPPLY SYSTEM | MBH | KW | MBH | 090102 | |||
This category includes both natural gas and LPG. Assemblies include metering and regulation equipment, storage equipment, transfer equipment, and distribution piping. The unit of measure at the assembly level is each system. | ||||||||
D301003 | STEAM SUPPLY SYSTEM (FROM CENTRAL PLANT) | MBH | KW | Power | 090104 | |||
Assemblies include meters, valves, heat exchangers, fittings, and specialties required for hook-up and distribution piping, including supports, sleeves, and insulation. The unit of measure at the assembly level is each system. | ||||||||
D301004 | HOT WATER SUPPLY SYSTEM (FROM CENTRAL PLANT) | MBH | KW | Power | 090105 | |||
Assemblies include meters, valves, heat exchangers, fittings, and specialties required for hook-up and distribution piping, including supports, sleeves, and insulation. The unit of measure at the assembly level is each system. | ||||||||
D301005 | SOLAR ENERGY SUPPLY SYSTEMS | EA | EA | Each System | 090106 | |||
Assemblies include collector panels, heat exchangers, storage tanks, pumps, etc., including pipe and fittings required for hook-up. The unit of measure at the assembly level is each system. | ||||||||
D301006 | WIND ENERGY SUPPLY SYSTEM | EA | EA | Each System | 090107 | |||
Wind is used to turn a generator which generates electricity. This energy is either stored in a battery or used to generate hot water in an electric boiler. Assemblies would include the required devices to make this a total electromechanical system. The unit of measure at the assembly level is each system. | ||||||||
D301007 | COAL SUPPLY SYSTEM | MBH | KW | Power | 090103 | |||
This category includes storage equipment, transfer equipment, processing equipment, and distribution piping. The unit of measure at the assembly level is each system. | ||||||||
D301090 | OTHER ENERGY SUPPLY | XX | XX | 09019X | ||||
Energy supply not described by the assembly categories listed above. | ||||||||
D3020 | HEAT GENERATING SYSTEMS | MBH | KW | Total power of heating system | 0902 | |||
This subsystem includes steam, hot water, furnace, and unit heater systems. Fuels include coal, oil, gas and electric unless otherwise noted. | ||||||||
D302001 | BOILERS | MBH | KW | Power | 090202 | |||
Assemblies include steam or hot water boilers, expansion tanks, chemical feeders, air separators, pumps, heat exchangers, boiler feed units, etc. This assembly would also include fittings and specialties and the flue stack. The unit of measure at the assembly level is each system. | ||||||||
D302002 | FURNACES | MBH | KW | Power | 090203 | |||
This is a system that heats air. Assemblies would include furnace and necessary fittings and specialties required for hook-up, including flue and stack. The unit of measure at the assembly level is each. | ||||||||
D302003 | FUEL-FIRED UNIT HEATERS | MBH | KW | Power | 090204 | |||
Assemblies would include unit heaters and the energy supply system hook-up (other than electrical), including all necessary pipe, fittings, and specialties required for hook-up. Flue and stack, if required, are included in this assembly. The unit of measure at the assembly level is each. | ||||||||
D302004 | AUXILIARY EQUIPMENT | MBH | KW | Power | 090205 | |||
Assemblies would include any other equipment associated with heat generating systems. The unit of measure at the assembly level is each. | ||||||||
D302005 | EQUIPMENT THERMAL INSULATION | SF | M2 | Area of insulation | 090206 | |||
Assemblies would include insulation of any component in this subsystem. The unit of measure at the assembly level is each. | ||||||||
D302090 | OTHER HEAT GENERATING SYSTEMS | XX | XX | 09029X | ||||
Heat generating systems not described in the assembly categories listed above. | ||||||||
D3030 | COOLING GENERATING SYSTEMS | TON | KW | Total power of cooling capacity | 0903 | |||
Cooling generating equipment of the absorption, centrifugal, reciprocating, and direct expansion types. | ||||||||
D303001 | CHILLED WATER SYSTEMS | TON | KW | Power | 090301 | |||
Assemblies include condensers, compressors, chillers, pumps, cooling towers, etc., including fittings and specialties required for hook-up. The unit of measure at the assembly level is each. | ||||||||
D303002 | DIRECT EXPANSION SYSTEMS | TON | KW | Power | 090302 | |||
Assemblies include condensers, compressors, heat pumps, and refrigerant piping. The unit of measure at the assembly level is each. | ||||||||
D303090 | OTHER COOLING GENERATING SYSTEMS | XX | XX | 09039X | ||||
Cooling generating systems not described by the assembly categories listed above. | ||||||||
D3040 | DISTRIBUTION SYSTEMS | MBH | KW | Power | 0904 | |||
This includes systems that distribute heated and cooled air, ventilating and exhaust air, hot and chilled water, steam, and glycol heating. | ||||||||
D304001 | AIR DISTRIBUTION, HEATING & COOLING | MCFM | L/S | Volume of air flow | 090401 | |||
Assemblies include heating coils, cooling coils, and fittings and specialties required for water hook-up. This assembly also includes duct heaters, filters, humidifiers, supply and return ductwork, dampers, fire dampers, supply and return grilles, registers and diffusers, turning vanes, sound traps, and all associated insulation. The unit of measure at the assembly level is MCFM. | ||||||||
D304002 | STEAM DISTRIBUTION SYSTEMS | MBH | KW | Power | 090402 | |||
Assemblies include pipe and fittings, supports, wall and floor sleeves, and pipe insulation. The unit of measure at the assembly level is MBH. | ||||||||
D304003 | HOT WATER DISTRIBUTION SYSTEMS | MBH | KW | Power | 090403 | |||
Assemblies include pipe and fittings, supports, wall and floor sleeves, and pipe insulation. The unit of measure at the assembly level is MBH. | ||||||||
D304004 | CHANGE OVER DISTRIBUTION SYSTEMS | MBH | KW | Power | 090404 | |||
D304005 | GLYCOL DISTRIBUTION SYSTEMS | MBH | KW | Power | 090405 | |||
Assemblies include pipe and fittings, supports, wall and floor sleeves, and pipe insulation. The unit of measure at the assembly level is MBH. | ||||||||
D304006 | CHILLED WATER DISTRIBUTION SYSTEMS | TON | KW | Power | 090406 | |||
Assemblies include pipe and fittings, supports, wall and floor sleeves, and pipe insulation. The unit of measure at the assembly level is tons. | ||||||||
D304007 | EXHAUST SYSTEMS | MCF | L/S | Volume of air flow | 090407 | |||
Assemblies include ductwork grilles, registers, diffusers, fans, and all associated work. The unit of measure at the assembly level is each system. | ||||||||
D304008 | AIR HANDLING UNITS | MCFM | L/S | Volume of air flow | ||||
D304090 | OTHER DISTRIBUTION SYSTEMS | XX | XX | 09049X | ||||
Distribution systems not described by the assembly categories listed above. | ||||||||
D3050 | TERMINAL & PACKAGE UNITS | MBH | KW | Power | 0905 | |||
This category includes self-contained heating and cooling units. | ||||||||
D305001 | UNIT VENTILATORS | EA | EA | Number of units | 090501 | |||
Assemblies include the complete terminal unit and wall sleeve with all controls. | ||||||||
D305002 | UNIT HEATERS | EA | EA | Number of units | 090502 | |||
Assemblies include the complete terminal unit and wall sleeve with all controls. | ||||||||
D305003 | FAN COIL UNITS | EA | EA | Number of units | 090503 | |||
Assemblies include the complete terminal unit and wall sleeve with all controls. | ||||||||
D305004 | FIN TUBE RADIATION | EA | EA | Number of units | 090504 | |||
Assemblies include the complete terminal unit and wall sleeve with all controls. | ||||||||
D305005 | ELECTRIC HEATING | EA | EA | Number of units | 090505 | |||
Assemblies include the complete terminal unit and wall sleeve with all controls. | ||||||||
D305006 | PACKAGE UNITS | EA | EA | Number of units | 090505 | |||
Assemblies include complete package units, with integral roof top curbs and all associated devices. A heating system can be selected from hot water, steam coil, or gas furnace and can be a single or multi-zone system. The unit of measure at the assembly level is each. | ||||||||
D305090 | OTHER TERMINAL & PACKAGE UNITS | XX | XX | 09059X | ||||
Terminal and package units not described by the assembly categories listed above. | ||||||||
D3060 | CONTROLS & INSTRUMENTATION | MBH | KW | Power | 0906 | |||
Includes devices such as thermostats, timers, sensors, control valves, etc., necessary to operate the system as designed. | ||||||||
D306001 | HVAC CONTROLS | EA | EA | Power | 090601 | |||
Includes devices such as thermostats, timers, sensors, control valves, etc., necessary to operate the total system. The unit of measure at the assembly level is each system. | ||||||||
D306002 | ELECTRONIC CONTROLS | EA | EA | Number of devices | ||||
D306003 | PNEUMATIC CONTROLS | EA | EA | Number of devices | ||||
Assemblies includes ball and butterfly valves, actuators, high pressure chokes, valve positioners, sensors, regulators, etc. | ||||||||
D306004 | INSTRUMENT AIR COMPRESSORS | EA | EA | Number of compressors | 090603 | |||
Assemblies include air compressors, dryers, and distribution tubing, (only used with pneumatic control systems). The unit of measure at the assembly level is each. | ||||||||
D306005 | GAS PURGING SYSTEMS | EA | EA | Number of systems | 090604 | |||
Assemblies include the removal of contaminated or unwanted gases from a structure or pipe. | ||||||||
D306090 | OTHER CONTROLS INSTRUMENTATION | XX | XX | 09069X | ||||
Controls and instrumentation not described by the assembly categories listed above. | ||||||||
D3070 | SYSTEMS TESTING & BALANCING | MBH | KW | Power | 0907 | |||
This includes operation of all systems to determine capacity and adjustment of water flow in chilled water and hot water systems, air flow of air handling units, supply and exhaust fans, and supply and return, and exhaust registers. | ||||||||
D307001 | WATER SIDE TESTING & BALANCING - HEATING & COOLING | EA | EA | Number of devices | 090701 | |||
Includes operating and testing of pumps, setting of all control valves, and determining system capacity. The unit of measure at the assembly level is each device, i.e., boiler, chiller, fan coil, and unit heater. | ||||||||
D307002 | AIR SIDE TESTING & BALANCING - HEATING, COOLING & EXHAUST | EA | EA | Number of devices | 090702 | |||
Includes operating and testing of all air handling devices, adjusting of all fans to set rate of air flow, setting all fan motors at desired operation, setting of air flow at all registers, grilles, diffusers, and louvers to deliver design CFM, and testing and calibrating of thermostats to achieve desired space temperature. The unit of measure at the assembly level is each device. | ||||||||
D307003 | HVAC COMMISSIONING | LS | LS | Lump sum | 090703 | |||
Final testing of operational system. | ||||||||
D307090 | OTHER SYSTEMS TESTING & BALANCING | XX | XX | 09079X | ||||
Systems testing and balancing not described by the assembly categories listed above. | ||||||||
D3090 | OTHER HVAC SYSTEMS AND EQUIPMENT | EA | EA | Number of special mechanical systems | 0908 | |||
This subsystem includes special mechanical systems that are not normally included as part of standard HVAC systems. | ||||||||
D309001 | GENERAL CONSTRUCTION ITEMS | SF | M2 | Area of special system | 090801 | |||
Includes construction work other than mechanical which must be performed in conjunction with the special mechanical system to make the system complete. | ||||||||
D309002 | REFRIGERATION SYSTEMS | TON | KW | Power | 090802 | |||
Includes equipment for refrigeration in a cold storage facility. Both low and medium temperature equipment are included. Assemblies include: condensing and compressor units, evaporator blowers, refrigerant piping, and specialties, heat recovery systems (liquid or gas), heat recovery distribution systems (liquid or gas), and system testing and balancing. | ||||||||
D309090 | OTHER SPECIAL MECHANICAL SYSTEMS | XX | XX | 09089X | ||||
Any other mechanical system not defined in other categories. Assemblies would include special systems and special devices. The unit of measure at the assembly level is each system or device. | ||||||||
D40 | FIRE PROTECTION | SF | M2 | Gross floor area | 10 | |||
This system includes standard and special fire protection systems. Fire alarm systems are included in D503001. | ||||||||
D4010 | FIRE ALARM AND DETECTION SYSTEMS | SF | M2 | Gross floor area | 1001 | |||
Assemblies include wire, conduit, conduit support or fastening systems, fire alarm devices, fire detection devices, safety switches, mass notification, all electrical connections and other associated items. | ||||||||
D401001 | FIRE ALARM DISTRIBUTION | SF | M2 | Gross floor area | 100201 | |||
Wire, conduit, conduit support or fastening systems, switches and connections. | ||||||||
D401002 | FIRE ALARM DEVICES | EA | EA | Number of devices | 100101 | |||
Fire alarm and fire detection devices | ||||||||
D4020 | FIRE SUPPRESSION WATER SUPPLY AND EQUIPMENT | LF | M | Length of system | 190104 | |||
Requirements for water supply design criteria and any items located upstream of the suppression systems such as PIV's, backflow preventers, strainers, etc. The water supply distribution system begins 5'-0" outside the building. | ||||||||
D402001 | FIRE PROTECTION WATER PIPING AND EQUIPMENT | LF | M | Length of system | 190104 | |||
Piping | ||||||||
D402002 | FIRE PUMP | EA | EA | Number of pumps | ||||
D4030 | STANDPIPE SYSTEMS | EA | EA | Number of sprinkler heads | 1003 | |||
This subsystem includes the complete standpipe system. | ||||||||
D403001 | STANDPIPE EQUIPMENT & PIPING | EA | EA | Number of sprinkler heads | 100301 | |||
Assemblies include standpipe risers and all other piping, fittings, and supports associated with this category. Siamese connections, roof manifolds, cabinets, hoses, racks, and other fire department connections are included in this assembly. All equipment including pumps, tanks, etc., with all required fittings and specialties for hook-up are included in this assembly. | ||||||||
D4040 | SPRINKLERS | EA | EA | Number of sprinkler heads | 1001 | |||
This subsystem includes the water supply equipment and related piping from the equipment to the sprinkler head. | ||||||||
D404001 | SPRINKLERS AND RELEASING DEVICES | EA | EA | Number of sprinkler heads | 100201 | |||
The fixture, device, or sprinkler head that releases the water to suppress the fire. The unit of measure at the assembly level is each sprinkler head. | ||||||||
D404002 | SPRINKLER WATER SUPPLY EQUIPMENT AND PIPING | EA | EA | Number of sprinkler heads | 100101 | |||
Assemblies include alarm valves, flow control valves, pipe and fittings from equipment to sprinkler heads, including all supports and wall or floor sleeves. All equipment including tanks, pumps, and other associated equipment, fittings and specialties required for hook-up are in this assembly. The unit of measure at the assembly level is each sprinkler head. | ||||||||
D4050 | FIRE PROTECTION SPECIALTIES | EA | EA | Number of extinguishers | 1004 | |||
This subsystem includes fire extinguishing devices. | ||||||||
D405001 | PORTABLE EXTINGUISHERS | EA | EA | Number of extinguishers | 100401 | |||
Assemblies include all types of fire extinguishers, i.e., water, dry chemical, carbon dioxide, soda acid, etc. The brackets, sleeves, and supporting devices are included in this assembly. | ||||||||
D4090 | OTHER FIRE PROTECTION SYSTEMS | EA | EA | Each system | 1005 | |||
Requirements for all other suppression systems. Water based systems (e.g., foam systems) specified from water supply onwards, complete specification for gas systems, incidental systems such as kitchen hood systems. | ||||||||
D409001 | CARBON DIOXIDE SYSTEMS | EA | EA | Number of systems | ||||
D409002 | FOAM GENERATING EQUIPMENT | EA | EA | Pieces of equipment | ||||
D409003 | CLEAN AGENT SYSTEMS | EA | EA | Number of systems | ||||
D409004 | HOOD & DUCT FIRE PROTECTION | EA | EA | Pieces of equipment | ||||
D409090 | OTHER SPECIAL FIRE PROTECTION SYSTEMS | EA | EA | Each system | 100501 | |||
Assemblies includes other fire protection systems such as halon systems, exhaust hood systems, and special chemical suppression systems. | ||||||||
D50 | ELECTRICAL | AMP | AMP | Gross floor area | 11 | |||
This system is defined by the electric current used or regarded as a source of power. | ||||||||
D5010 | ELECTRICAL SERVICE & DISTRIBUTION | AMP | AMP | Gross floor area | 1101 | |||
This subsystem provides for all electrical devices that are required to deliver the main source of power to the facility and to distribute this power to subpanels. | ||||||||
D501001 | MAIN TRANSFORMERS | AMP | AMP | Number of transformers | 110101 | |||
Transformers used for primary electrical service and located within the building footprint. Assemblies include transformers, raised pad, trenching, and backfill. This assembly will not likely be used when an exterior transformer is required in G4010 ELECTRICAL DISTRIBUTION. | ||||||||
D501002 | SERVICE ENTRANCE EQUIPMENT | AMP | AMP | Gross floor area | 110103 | |||
This includes the protection equipment and metering devices for main distribution. Assemblies include main distribution panel, breaker, fuses, and meters. | ||||||||
D501003 | INTERIOR DISTRIBUTION TRANSFORMERS | AMP | AMP | Gross floor area | 110104 | |||
Transformers fed downstream of the service entrance equipment. Assemblies include transformers, conduit, conduit support, and wire. | ||||||||
D501004 | PANELBOARDS | AMP | AMP | Gross floor area | 110105 | |||
Branch circuit panelboards. Assemblies include panelboards, breakers ,conduit, and wire. | ||||||||
D501005 | ENCLOSED CIRCUIT BREAKERS | AMP | AMP | Gross floor area | 110106 | |||
Over-current protection device enclosed in its own housing. Assemblies include enclosed circuit breaker, conduit, and wire. | ||||||||
D501006 | MOTOR CONTROL CENTERS | AMP | AMP | Gross floor area | 110107 | |||
This is a cabinet in which motor starters and operation devices are contained. Assemblies include the motor control center cabinet, motor starters, contacts, switches, conduit, wire, and all associated items. | ||||||||
D501090 | OTHER SERVICE AND DISTRIBUTION | XX | XX | 11019X | ||||
Service and distribution not described by the assembly categories listed above. | ||||||||
D5020 | LIGHTING & BRANCH WIRING | SF | M2 | Floor area | 1102 | |||
Lighting systems including light fixtures and devices, i.e., switches, receptacles, and equipment connections. | ||||||||
D502001 | BRANCH WIRING | SF | M2 | Floor area | 110201 | |||
This assembly includes switches, receptacles, equipment connections, conduit, and wire. | ||||||||
D502002 | LIGHTING EQUIPMENT | SF | M2 | Floor area | 110202 | |||
This assembly includes fixtures, conduit, wire, and switching devices. | ||||||||
D502090 | OTHER LIGHTING AND BRANCH WIRING | XX | XX | 11029X | ||||
Lighting and branch wiring not described by the assembly categories listed above. | ||||||||
D5030 | COMMUNICATIONS & SECURITY | SF | M2 | Floor area | 1201 | |||
This subsystem includes provisions for communication devices and alarm protection systems. | ||||||||
D503001 | TELECOMMUNICATIONS SYSTEMS | EA | EA | Number of outlets | 120103 | |||
This system would include central switchboards, telephone sets, underground ducts, and manholes. Assemblies include wire, conduit, backboards, cabinets, outlets, and power supply connections. | ||||||||
D503002 | PUBLIC ADDRESS SYSTEMS | SF | M2 | Floor area | 120104 | |||
Assemblies include wire, conduit, speakers, monitoring devices, amplifiers, switches, power system tie-in devices, and detection devices. | ||||||||
D503003 | INTERCOMMUNICATIONS SYSTEMS | EA | EA | Number of stations | 120105 | |||
Assemblies include wire, conduit, speakers, monitoring devices, amplifiers, switches, power system tie-in devices, and detection devices. | ||||||||
D503004 | TELEVISION SYSTEMS | EA | EA | Number of outlets | 120107 | |||
Assemblies include wire, conduit, grounding amplifiers, receivers, video equipment, and outlets grouped according to use. | ||||||||
D503005 | SECURITY SYSTEMS | EA | EA | Number of system control panels | 120108 | |||
Assemblies include wire, conduit, conduit support or fastening systems, security alarm devices, all electrical connections, and other associated items. Intrusion Detection Systems (IDS) are included in this category. | ||||||||
D503006 | NURSE CALL SYSTEMS | EA | EA | Number of outlets | 120102 | |||
Assemblies include wire, conduit, speakers, monitoring devices, amplifiers, switches, power system tie-in devices, and detection devices. | ||||||||
D503007 | CLOCK & PROGRAM SYSTEMS | EA | EA | Number of clocks | 120106 | |||
Assemblies include wire, conduit, power systems tie-in, safety switches, control panels, battery back-up devices, clocks and outlets. | ||||||||
D503090 | OTHER COMMUNICATIONS & ALARM SYSTEMS | XX | XX | 12019X | ||||
Communication and alarm systems not described by the assembly categories listed above. | ||||||||
D5090 | OTHER ELECTRICAL SERVICES | SF | M2 | Gross Floor area | 1202 | |||
Systems not described in System D5030. | ||||||||
D509001 | GENERAL CONSTRUCTION ITEMS (ELECTRICAL) | SF | M2 | Gross Floor area | 120201 | |||
Includes construction other than electrical which must be performed in conjunction with the special electrical system to make the system complete. | ||||||||
D509002 | EMERGENCY LIGHTING & POWER | SF | M2 | Gross Floor area | 120202 | |||
Assemblies include fixtures, motors used for power generation, connection and testing, transfer switches, conduit, wire, battery chargers, batteries, and solar panels. | ||||||||
D509003 | GROUNDING SYSTEMS | SF | M2 | Gross Floor area | 120203 | |||
This assembly includes grounding protection systems. | ||||||||
D509004 | LIGHTNING PROTECTION | SF | M2 | Gross Floor area | 120204 | |||
Assemblies include lightning protection devices (air terminals, mounting devices), clamps, ground rods, cadwells, conductors, trenching, backfill, and any other items used to ground metal structural frames with conduit and wire. | ||||||||
D509005 | ELECTRIC HEATING | SF | M2 | Gross Floor area | 120205 | |||
Items could include baseboard heaters and wall and ceiling heaters. Assemblies include safety switches, control devices, heaters, conduit, and wire. | ||||||||
D509006 | ENERGY MANAGEMENT CONTROL SYSTEM | SF | M2 | Gross Floor area | 120206 | |||
Assemblies include wire, conduit, conduit support or fastening systems, sensor devices, and all electrical connections. | ||||||||
D509090 | OTHER SPECIAL SYSTEMS AND DEVICES | XX | XX | 12029X | ||||
Special systems and devices not described by the assembly categories listed above. |
Unf L1 | Unf L2 | Unf L3 | WBS L4 | Definition | E UOM | M UOM | Quantity Definition | WBS Ref No |
---|---|---|---|---|---|---|---|---|
E | EQUIPMENT & FURNISHINGS | SF | M2 | Gross Floor Area | ||||
The types of equipment included in this assembly consist of the following: commercial, institutional, and vehicular. The types of furnishings found here include artwork, window treatments, seating, furniture, rugs etc. | ||||||||
E10 | EQUIPMENT | SF | M2 | Gross Floor area | 13 | |||
This system refers to equipment not found in System C1030 (Fittings). | ||||||||
E1010 | COMMERCIAL EQUIPMENT | SF | M2 | Floor area | 1301 | |||
This equipment is not likely to be used in every building type. Subsystem C1030 includes those items likely to be found in every building type. | ||||||||
E101001 | CHECKROOM EQUIPMENT | EA | EA | Number of coat hanging devices | 130102 | |||
All associated work items including keys, tags, and storage cabinets would be included in this assembly. | ||||||||
E101002 | REGISTRATION EQUIPMENT | EA | EA | Pieces of equipment | 130114 | |||
E101003 | VENDING EQUIPMENT | EA | EA | Pieces of equipment | 130104 | |||
E101004 | LAUNDRY EQUIPMENT | EA | EA | Pieces of equipment | 130116 | |||
E101005 | SECURITY & VAULT EQUIPMENT | EA | EA | Pieces of equipment | 130117 | |||
E101006 | TELLER AND SERVICE EQUIPMENT | EA | EA | Pieces of equipment | ||||
E101007 | MERCANTILE EQUIPMENT | EA | EA | Pieces of equipment | ||||
E101008 | OFFICE EQUIPMENT | EA | EA | Pieces of equipment | ||||
E1020 | INSTITUTIONAL EQUIPMENT | SF | M2 | Floor area | ||||
Institutional equipment includes items that are normally found in hospitals, laboratories, auditoriums, and libraries. | ||||||||
E102001 | MISCELLANEOUS COMMON FIXED & MOVEABLE EQUIPMENT | EA | EA | Pieces of equipment | 130108 | |||
E102002 | MEDICAL EQUIPMENT | EA | EA | Pieces of equipment | 130110 | |||
E102003 | LABORATORY EQUIPMENT | EA | EA | Pieces of equipment | 130111 | |||
E102004 | MORTUARY EQUIPMENT | EA | EA | Pieces of equipment | 130112 | |||
E102005 | AUDITORIUM & STAGE EQUIPMENT | EA | EA | Pieces of equipment | 130113 | |||
E102006 | LIBRARY EQUIPMENT | EA | EA | Pieces of equipment | 130115 | |||
E102007 | ECCLESIASTICAL EQUIPMENT | EA | EA | Pieces of equipment | ||||
E102008 | INSTRUMENTAL EQUIPMENT | EA | EA | Pieces of equipment | ||||
E102009 | AUDIO-VISUAL EQUIPMENT | EA | EA | Pieces of equipment | ||||
E102010 | DETENTION EQUIPMENT | EA | EA | Pieces of equipment | ||||
E1030 | VEHICULAR EQUIPMENT | EA | EA | Pieces of equipment | ||||
Vehicular equipment includes for parking, loading docks, and warehouses. | ||||||||
E103001 | PARKING CONTROL EQUIPMENT | EA | EA | Pieces of equipment | 130107 | |||
E103002 | LOADING DOCK EQUIPMENT | EA | EA | Number of docks | 130106 | |||
E103003 | WAREHOUSE EQUIPMENT | EA | EA | Pieces of equipment | 130109 | |||
E103004 | AUTOMOTIVE SHOP EQUIPMENT | EA | EA | Pieces of equipment | 0 | |||
E1040 | GOVERNMENT FURNISHED EQUIPMENT | EA | EA | Pieces of equipment | ||||
New and existing equipment provided to the Contractor by the Government. | ||||||||
E1090 | OTHER EQUIPMENT | |||||||
The type of equipment found in his category include items for maintenance, food service, and waste handling. | ||||||||
E109001 | BUILT-IN MAINTENANCE EQUIPMENT | SF | M2 | Floor area | 130101 | |||
The unit of measure at the assembly level is each. | ||||||||
E109002 | FOOD SERVICE EQUIPMENT | EA | EA | Seating capacity | 130103 | |||
The unit of measure at the assembly level is the total set of equipment needed in the particular functional space area. | ||||||||
E109003 | WASTE HANDLING EQUIPMENT | EA | EA | Pieces of equipment | 130105 | |||
E109004 | RESIDENTIAL EQUIPMENT | EA | EA | Pieces of equipment | ||||
E109005 | UNIT KITCHENS | EA | EA | Pieces of equipment | ||||
E109006 | DARKROOM EQUIPMENT | EA | EA | Pieces of equipment | ||||
E109007 | ATHLETIC, RECREATIONAL, & THERAPEUTIC EQUIPMENT | EA | EA | Pieces of equipment | ||||
E109008 | PLANETARIUM EQUIPMENT | EA | EA | Pieces of equipment | ||||
E109009 | OBSERVATORY EQUIPMENT | EA | EA | Pieces of equipment | ||||
E109010 | AGRICULTURAL EQUIPMENT | EA | EA | Pieces of equipment | ||||
E109090 | OTHER SPECIALIZED FIXED AND MOVEABLE EQUIPMENT | XX | XX | 13019X | ||||
Specialized fixed and moveable equipment not described by the assembly categories listed above. | ||||||||
E20 | FURNISHINGS | SF | M2 | Floor area | 14 | |||
The types of furnishings found here include artwork, window treatments, seating, furniture, rugs, etc. | ||||||||
E2010 | FIXED FURNISHINGS | SF | M2 | Floor area | 1401 | |||
The types of furnishings found here include artwork, window treatments, and seating. | ||||||||
E201001 | FIXED ARTWORK | EA | EA | Pieces of art work | 140102 | |||
E201002 | WINDOW TREATMENTS | SF | M2 | Area of window treatment | 140103 | |||
E201003 | SEATING (FIXED) | EA | EA | Number of seats | 140104 | |||
E201004 | FIXED INTERIOR LANDSCAPING | EA | EA | Number of items | ||||
E201090 | OTHER FIXED INTERIOR FURNISHINGS | EA | EA | Number of furnishings | 14019X | |||
E2020 | MOVEABLE FURNISHINGS | |||||||
The types of furnishings found here include moveable artwork, furniture, rugs, etc. | ||||||||
E202001 | MOVEABLE ART WORK | EA | EA | Pieces of art work | ||||
E202002 | MODULAR PREFABRICATED FURNITURE | SF | M2 | Pieces of prefabricated furniture | 140101 | |||
E202003 | FREESTANDING FURNITURE | EA | EA | Pieces of furniture | ||||
E202004 | RUGS & ACCESSORIES | EA | EA | Number of rugs, mats, accessories | 140105 | |||
Assemblies include rugs and accessories. | ||||||||
E202005 | MOVEABLE MULTIPLE SEATING | EA | EA | Number of items | ||||
E202006 | MOVEABLE INTERIOR LANDSCAPING | EA | EA | Number of items | ||||
E202090 | OTHER MOVEABLE FURNISHINGS | EA | EA | Number of furnishings |
Unf L1 | Unf L2 | Unf L3 | WBS L4 | Definition | E UOM | M UOM | Quantity Definition | WBS Ref No |
---|---|---|---|---|---|---|---|---|
F | SPECIAL CONSTRUCTION & DEMOLITION | SF | M2 | Floor area | ||||
Special construction includes air-supported structures; pre-engineered structures; special purpose rooms; sound, vibration, and seismic construction; radiation protection; special security systems; aquatic facilities; ice rinks, site constructed incinerators; kennels and animal shelters; liquid and gas storage tanks; recording instrumentation; and building automation systems. Selective building demolition includes demolition of existing buildings, and site demolition. | ||||||||
F10 | SPECIAL CONSTRUCTION | SF | M2 | Floor area | 15 | |||
Special construction includes air-supported structures; pre-engineered structures; special purpose rooms; sound, vibration, and seismic construction; radiation protection; special security systems; aquatic facilities; ice rinks, site constructed incinerators; kennels and animal shelters; liquid and gas storage tanks; recording instrumentation; and building automation systems. | ||||||||
F1010 | SPECIAL STRUCTURES | SF | M2 | Floor area | ||||
Special structures includes air-supported structures, and pre-engineered structures. | ||||||||
F101001 | METAL BUILDING SYSTEMS | SF | M2 | Floor area | 1504 | |||
F101002 | EXTERIOR UTILITY BUILDINGS | SF | M2 | Floor area of exterior building | 1506 | |||
F101003 | AIR-SUPPORTED STRUCTURES | SF | M2 | Floor area of exterior building | ||||
F101090 | OTHER SPECIAL CONSTRUCTION | XX | XX | |||||
F1020 | INTEGRATED CONSTRUCTION | SF | M2 | Floor area | ||||
Integrated construction includes integrated assemblies and special purpose rooms. | ||||||||
F102001 | SPECIAL PURPOSE ROOMS | SF | M2 | Area of room | 1503 | |||
F102002 | INTEGRATED ASSEMBLIES | SF | M2 | Area of room | ||||
F102090 | OTHER INTEGRATED CONSTRUCTION | SF | M2 | Area of room | ||||
F1030 | SPECIAL CONSTRUCTION SYSTEMS | SF | M2 | Area of room | ||||
Special construction systems includes sound, vibration, and seismic construction; radiation protection; special security systems; and built-in place vaults. | ||||||||
F103001 | VAULTS | SF | M2 | Area of vault | 1501 | |||
This is a built-in-place vault. Prefabricated safes are not included in this assembly. The unit of measure at the assembly level is each. | ||||||||
F103002 | SOUND, VIBRATION, AND SEISMIC CONSTRUCTION | SF | M2 | Area of room | ||||
F103003 | RADIATION PROTECTION | SF | M2 | Area of room | ||||
F103090 | OTHER SPECIAL CONSTRUCTION SYSTEMS | SF | M2 | Area of room | ||||
F1040 | SPECIAL FACILITIES | SF | M2 | Area of room | ||||
Special facilities includes aquatic facilities; ice rinks, site constructed incinerators; kennels and animal shelters; and liquid and gas storage tanks. | ||||||||
F104001 | INTERIOR SWIMMING POOLS | SF | M2 | Area of pool | 1502 | |||
F104002 | LIQUID AND GAS STORAGE TANKS | EA | EA | Number of storage tanks | ||||
F104003 | KENNELS AND ANIMAL SHELTERS | SF | M2 | Area of kennel or animal shelter | ||||
F104004 | SITE CONSTRUCTED INCINERATORS | EA | EA | Number of incinerators | ||||
F104005 | ICE RINKS | SF | M2 | Area of ice rink | ||||
F104090 | OTHER SPECIAL FACILITIES | EA | EA | Number of special facilities | ||||
F1050 | SPECIAL CONTROLS AND INSTRUMENTATION | XX | XX | |||||
Special controls and instrumentation includes recording instrumentation and building automation systems. | ||||||||
F105001 | RECORDING INSTRUMENTATION | EA | EA | Number of instruments | ||||
F105002 | BUILDING AUTOMATION SYSTEMS | EA | EA | Number of systems | ||||
F105090 | OTHER SPECIAL CONTROLS AND INSTRUMENTATION | EA | EA | Number of controls and instruments | ||||
F20 | SELECTIVE BUILDING DEMOLITION | LS | LS | 16 | ||||
Selective building demolition includes demolition of existing buildings, site demolition, and hazardous components abatement. | ||||||||
F2010 | BUILDING ELEMENTS DEMOLITION | LS | LS | 1601 | ||||
Selective building demolition includes demolition of existing buildings, and site demolition. | ||||||||
F201001 | SUBSTRUCTURE & SUPERSTRUCTURE | LS | LS | 160101 | ||||
F201002 | EXTERIOR CLOSURE | LS | LS | 160102 | ||||
F201003 | ROOFING | LS | LS | 160103 | ||||
F201004 | INTERIOR CONSTRUCTION & FINISHES | LS | LS | 160104 | ||||
F201005 | CONVEYING SYSTEMS | LS | LS | 160105 | ||||
F201006 | MECHANICAL SYSTEMS | LS | LS | 160106 | ||||
F201007 | ELECTRICAL SYSTEMS | LS | LS | 160107 | ||||
F201008 | EQUIPMENT & FURNISHINGS | LS | LS | 160108 | ||||
F201090 | OTHER NON-HAZARDOUS SELECTIVE BUILDING DEMOLITION | XX | XX | 16019X | ||||
Non-hazardous selective building demolition not described by the assembly categories listed above. | ||||||||
F2020 | HAZARDOUS COMPONENTS ABATEMENT | LS | LS | 1602 | ||||
Hazardous components abatement includes the removal or encapsulation of hazardous building materials and components. Hazardous components include asbestos, lead based paint, paint containing cadmium, chromium and lead, mercury and low level radioactive components, PCBs, ozone depleting substances, animal droppings and molds and spores. | ||||||||
F202001 | SUBSTRUCTURE & SUPERSTRUCTURE | LS | LS | 160201 | ||||
F202002 | EXTERIOR CLOSURE | LS | LS | 160202 | ||||
F202003 | ROOFING | LS | LS | 160203 | ||||
F202004 | INTERIOR CONSTRUCTION & FINISHES | LS | LS | 160204 | ||||
F202005 | CONVEYING SYSTEMS | LS | LS | 160205 | ||||
F202006 | MECHANICAL SYSTEMS | LS | LS | 160206 | ||||
F202007 | ELECTRICAL SYSTEMS | LS | LS | 160207 | ||||
F202008 | EQUIPMENT & FURNISHINGS | LS | LS | 160208 | ||||
F202090 | OTHER HAZARDOUS SELECTIVE BUILDING DEMOLITION | XX | XX | 16029X | ||||
Hazardous selective building demolition not described by the assembly categories listed above. |
Unf L1 | Unf L2 | Unf L3 | WBS L4 | Definition | E UOM | M UOM | Quantity Definition | WBS Ref No |
---|---|---|---|---|---|---|---|---|
G | BUILDING SITEWORK | ACR | Hectare | Total area of site | ||||
Building sitework includes site preparations, site improvements, site civil/mechanical utilities, site electrical utilities, service and pedestrian tunnels, and other site construction, such as bridges, and railroad spurs. | ||||||||
G10 | SITE PREPARATIONS | ACR | Hectare | Total area of site | 17 | |||
This system includes assemblies for miscellaneous sitework such as clearing and grubbing, demolition and relocation, various earthwork tasks, and other site preparation and cleanup requirements. Hazardous cleanup is not included but is the subject of another WBS. | ||||||||
G1010 | SITE CLEARING | ACR | Hectare | Area to be cleared | 1701 | |||
This covers the different assemblies and options available for clearing of a site, tree and stump removal, burning, grubbing, chipping, and load and haul assemblies for removal of the cleared material. | ||||||||
G101001 | CLEARING | ACR | Hectare | Area to be cleared | 170101 | |||
This is the removal of above ground vegetation including stumps. For a wet site, Low Ground Pressure (LGP) equipment is used. | ||||||||
G101002 | TREE REMOVAL | EA | EA | Number of trees to be removed | 170102 | |||
This is the selective removal of trees on the site. Various options exist for different sizes of trees to be removed. | ||||||||
G101003 | STUMP REMOVAL | EA | EA | Number of stumps to be removed | 170103 | |||
This is the selective removal of stumps on the site. Various options exist for different sizes of stumps to be removed. | ||||||||
G101004 | GRUBBING | ACR | Hectare | Area to be grubbed | 170105 | |||
Grubbing is the removal of sod and other topsoil that contains unsuitable organic material. Various equipment types and size choices are available. Wet grubbing utilizes Low Ground Pressure (LGP) equipment. Haul-off of grubbed material is also included. | ||||||||
G101005 | SELECTIVE THINNING | ACR | Hectare | Area to be thinned | 170106 | |||
This is the selective removal of trees and underbrush without requiring extensive clearing and/or grubbing of the site. | ||||||||
G101006 | DEBRIS DISPOSAL | CY | M3 | Volume of material | 170107 | |||
This is the disposal of the material that has been cleared and grubbed. Loading, hauling, and dump charges are included. | ||||||||
G101090 | OTHER SITE CLEARING | XX | XX | 17019X | ||||
Site clearing not described by the assembly categories listed above. | ||||||||
G1020 | SITE DEMOLITION & RELOCATIONS | SY | M2 | Area to be demolished | 1702 | |||
This includes the demolition and/or relocation of structures, pavements, fencing, and underground utilities. Disposal of debris or demolished material, including loading and hauling, is also included. | ||||||||
G102001 | BUILDING MASS DEMOLITION | CF | M3 | Interior volume of building | 170201 | |||
This is the complete demolition of buildings or structures. Options include steel, concrete, masonry, and wood structures. | ||||||||
G102002 | ABOVE GROUND SITE DEMOLITION | SY | M2 | Area to be demolished | 170202 | |||
This is the demolition of pavements, fencing, and other non-building structures on a site. Pavement include roads, sidewalks, driveways, and curbs. Fencing types include chain link, barbed wire, and wood. This can also include removal and disposal of above ground storage tanks, including tank contents, associated piping, etc. | ||||||||
G102003 | UNDERGROUND SITE DEMOLITION | SY | M2 | Area to be demolished | 170203 | |||
This is the demolition of underground utilities such as piping, manholes, and other non-building underground structures. The unit of measure at the assembly level for piping is LF and for manholes is CY. This can also include removal and disposal of under ground storage tanks, including tank contents, associated piping, etc. | ||||||||
G102004 | BUILDING RELOCATION | SF | M2 | Area of building to be relocated | 170205 | |||
This is the process of dismantling a structure, and reassembling it on a different site. | ||||||||
G102005 | UTILITY RELOCATION | LF | M | Length of pipe run | 170206 | |||
To remove and reset. This is the removal and relocation of underground utilities such as steel and concrete pipe. | ||||||||
G102006 | FENCING RELOCATION | LF | M | Length of fencing | 170207 | |||
G102007 | SITE CLEANUP | SY | M2 | Area of site to clean | 170401 | |||
Covered in this assembly category are items for site and area cleanup and pavement sweeping. Disposal of the debris is also included. | ||||||||
G102090 | OTHER SITE DEMOLITION & RELOCATIONS | XX | XX | 17029X | ||||
Site demolition and relocation not described by the assembly categories listed above. | ||||||||
G1030 | SITE EARTHWORK | CY | M3 | Volume of material | 1703 | |||
Included are assemblies and options for site work such as grading, excavation, filling, compaction, stabilization, etc. | ||||||||
G103001 | GRADING | SY | M2 | Area to be graded | 170301 | |||
Grading is leveling or flattening of the site in preparation for landscaping or other site construction. Includes unlined stormwater collection ponds. | ||||||||
G103002 | COMMON EXCAVATION | CY | M3 | Volume of material to be excavated | 170302 | |||
This is excavation for roads, sidewalks, curbs, and trenching for underground utilities. Excavation may be carried out by a variety of equipment sizes and types. Disposal of the excavated material is also included. | ||||||||
G103003 | ROCK EXCAVATION | CY | M3 | Volume of rock to be excavated | 170303 | |||
This is excavation of rock by explosives. Different equipment selections and load and haul are included. | ||||||||
G103004 | FILL & BORROW | CY | M3 | Volume of material to place | 170304 | |||
This is filling or replacing the material that was removed during excavation. Either the excavated material may be used or soil and sand may be hauled in from off-site. Filling to basements and foundations is not included in the subsystem. | ||||||||
G103005 | COMPACTION | CY | M3 | Volume of material to compact | 170305 | |||
Compaction is the process of packing the fill material once it is in place. This may be done by machine or hand. Assemblies exist for both hand and machine compaction of soil, sand, and the excavated material. | ||||||||
G103006 | SOIL STABILIZATION | CY | M3 | Volume of soil to stabilize | 170306 | |||
This is stabilization of the soil-in-place by the addition of lime or cement. | ||||||||
G103007 | SLOPE STABILIZATION | SY | M2 | Area of slope | 170307 | |||
This is stabilization of the soil-in-place through the use of rip rap, gabions, slope paving, or other forms of soil armoring. | ||||||||
G103008 | SOIL TREATMENT | SY | M2 | Area of soil to treat | 170308 | |||
Treatment of soil prior to final construction for insect protection or other purposes. | ||||||||
G103009 | SHORING | SF | M2 | Area requiring shoring | 170309 | |||
Shoring is the temporary support for existing structures or excavation during construction. | ||||||||
G103010 | TEMPORARY DEWATERING | SY | M2 | Area to dewater | 170310 | |||
This is the dewatering of the site by wellpoints to lower the groundwater table. This will facilitate excavation in areas with high water tables. | ||||||||
G103011 | TEMPORARY EROSION & SEDIMENT CONTROL | SF | M2 | Area to be protected | 170311 | |||
Interim measures to minimize erosion during construction. | ||||||||
G103090 | OTHER SITE EARTHWORK | XX | XX | 17039X | ||||
Site earthwork not described by the assembly categories listed above. | ||||||||
G1040 | HAZARDOUS WASTE REMEDIATION | LS | LS | |||||
Hazardous waste remediation, removal, disaposal and restoration of contaminated soil and/or groundwater. | ||||||||
G104001 | REMOVAL OF CONTAMINATED SOIL | CY | M3 | Volume of contaminated soil | ||||
G104002 | SOIL RESTORATION AND TREATMENT | CY | M3 | Volume of soil | ||||
G104090 | OTHER HAZARDOUS WASTE REMEDIATION | XX | XX | |||||
Hazardous waste remediation not described by the assembly categories listed above. | ||||||||
G20 | SITE IMPROVEMENTS | LS | LS | 18 | ||||
This includes improvements such as parking lots, sidewalks, roadways, fencing, retaining walls, and landscaping. | ||||||||
G2010 | ROADWAYS | SY | M2 | Area of roadway | 1801 | |||
This subsystem includes options for access, arterial, or interstate roadways. A variety of pavement types and thickness are available. | ||||||||
G201001 | BASES & SUBBASES | SY | M2 | Area of roadway | 180101 | |||
These are the compacted and prepared gravel or soil layers that are placed prior to the installation of the final surface. The subbase is placed and compacted before the base layer is applied. | ||||||||
G201002 | CURBS & GUTTERS | LF | M | Length of drainage pipe | ||||
This is the drainage system for the selected roadway type. Options include curb and gutter drains or area drains with grates. | ||||||||
G201003 | PAVED SURFACES | SY | M2 | Area of roadway | 180103 | |||
This is material that is placed atop the base layer to provide the driving surface. | ||||||||
G201004 | MARKING & SIGNAGE | SY | M2 | Area of roadway | 180104 | |||
This includes roadway signage and pavement painting. Assemblies are included for traffic signs and posts and intersection, crosswalk, or other pavement painting or striping. | ||||||||
G201005 | GUARDRAILS & BARRIERS | LF | M | Length of guardrail or barrier | 180105 | |||
This is any associated guardrails or barriers that are required for the selected roadway type. | ||||||||
G201006 | RESURFACING | SY | M2 | Area of roadway | 180106 | |||
This is the placement of an asphalt wearing course over the existing pavement surface. Assemblies exist for resurfacing of gravel, concrete, and asphalt roadways. | ||||||||
G201090 | OTHER ROADWAYS | XX | XX | 18019X | ||||
Roadways not described by the assembly categories listed above. | ||||||||
G2020 | PARKING LOTS | EA | EA | Number of spaces | 1802 | |||
These are the areas required of vehicles parking and include different surfaces and drainage options. | ||||||||
G202001 | BASES & SUBBASES | SY | M2 | Area of parking lot | 180201 | |||
These are the compacted and prepared gravel or soil layers that are placed prior to the installation of the final surface. The subbase is placed and compacted before the base layer is applied. | ||||||||
G202002 | CURBS & GUTTERS | LF | M | Length of curbs & gutters | ||||
This is the curb and gutter drains or area drains with grates. | ||||||||
G202003 | PAVED SURFACES | SY | M2 | Area of parking lot | 180203 | |||
This is material that is placed atop the base layer to provide the driving surface. | ||||||||
G202004 | MARKING & SIGNAGE | EA | EA | Number of spaces | 180205 | |||
This includes painting of the parking stalls, signage, etc. | ||||||||
G202005 | GUARDRAILS & BARRIERS | LF | M | Length of guardrail or barrier | 180205 | |||
Guardrails, barriers, parking stops and other similar devices. | ||||||||
G202006 | RESURFACING | SY | M2 | Area of parking lot | 180206 | |||
This is the placement of an asphalt wearing course over the existing parking surface. | ||||||||
G202007 | MISCELLANEOUS STRUCTURES AND EQUIPMENT | EA | EA | Number of structures or equipment | ||||
G202090 | OTHER PARKING LOTS | XX | XX | 18029X | ||||
Parking areas not described by the assembly categories listed above. | ||||||||
G2030 | PEDESTRIAN PAVING | SY | M2 | Area of pavement | 1803 | |||
This subsystem includes options for sidewalks and other small paved areas. | ||||||||
G203001 | BASES & SUBBASES | SY | M2 | Area of pavement | 180301 | |||
These are the compacted and prepared gravel or soil layers that are placed prior to the installation of the final surface. The subbase is placed and compacted before the base layer is applied. | ||||||||
G203002 | CURBS & GUTTERS | LF | M | Length of curbs & gutters | ||||
This is the curb and gutter drains or area drains with grates. | ||||||||
G203003 | PAVED SURFACES | SY | M2 | Area of pavement | 180303 | |||
This is material that is placed atop the base layer to provide the walking or driving surface. | ||||||||
G203004 | GUARDRAILS & BARRIERS | LF | M | Length of guardrail or barrier | 180304 | |||
This is any associated guardrails or barriers that are required. | ||||||||
G203005 | RESURFACING | SY | M2 | Area of pavement | 180305 | |||
This is the placement of an asphalt wearing course over the existing pavement surface. | ||||||||
G203090 | OTHER WALKS, STEPS & TERRACES | XX | XX | 18039X | ||||
Walks, steps, ramps, terraces not described by the assembly categories listed above. | ||||||||
G2040 | SITE DEVELOPMENT | EA | EA | Each Structure | 1804 | |||
Included are assemblies for on-site construction of fences, retaining walls, playing fields, fountains, and other site improvements. | ||||||||
G204001 | FENCING & GATES | LF | M | Length of fence | 180401 | |||
This includes installation or construction of security, boundary, or barbed wire fencing and all required gates. | ||||||||
G204002 | RETAINING WALLS AND FREESTANDING WALLS | SY | M2 | Area of wall | 180402 | |||
These are structures used to prevent the flow or lateral movement of soil. Assemblies exist for cast-in-place concrete retaining walls. | ||||||||
G204003 | EXTERIOR FURNISHINGS | EA | EA | Number of furnishings | 180403 | |||
This includes the addition of such exterior furnishings as benches, planters, etc. | ||||||||
G204004 | SECURITY STRUCTURES | EA | EA | Number of security structures | 180404 | |||
This includes the construction or addition of security structures such as guard houses. | ||||||||
G204005 | SIGNAGE | EA | EA | Number of signs | 180405 | |||
Signs displayed to convey direction or information such as building function or tenant except for signs included in G201004 and G202004. | ||||||||
G204006 | FOUNTAINS & POOLS | EA | EA | Number of fountains or pools | 180406 | |||
This includes assemblies for swimming pools and decorative fountains. | ||||||||
G204007 | PLAYING FIELDS | EA | EA | Number of playing fields | 180407 | |||
Playing fields such as baseball or tennis courts as well as back stops, bleachers, and other playing field requirements are included. | ||||||||
G204008 | TERRACE AND PERIMETER WALLS | SY | M2 | Area of wall | ||||
G204009 | FLAGPOLES | EA | EA | Number of flagpoles | ||||
G204090 | OTHER SITE IMPROVEMENTS | XX | XX | 1804 | ||||
This includes any other miscellaneous structures, such as a car wash, banking system, and theatre equipment located on the site. | ||||||||
G2050 | LANDSCAPING | SY | M2 | Area to be landscaped | 1805 | |||
Assemblies are included that improve the appearance of the site by planting, seeding, and sodding. | ||||||||
G205001 | FINE GRADING & SOIL PREPARATION | SY | M2 | Area of site | 180501 | |||
Fine grading of the site by hand or machine is required to prepare the soil for planting, seeding, or sodding. | ||||||||
G205002 | EROSION CONTROL MEASURES | SY | M2 | Area of erosion | 180502 | |||
Soil erosion or deterioration due to wind, rain or other factors can be controlled or remedied in different ways. This includes slope protection by planting or vegetation or grass and/or placement of manmade geotextiles. | ||||||||
G205003 | TOPSOIL & PLANTING BEDS | SY | M2 | Area of planting bed | 180503 | |||
Topsoil is placed to provide the nutritious soil bed which is required for plants or grass to grow. | ||||||||
G205004 | SEEDING, SPRIGGING AND SODDING | SY | M2 | Area of site | 180504 | |||
This includes the seeding, sodding, fertilizing, watering, and mowing for the grass required on site. | ||||||||
G205005 | PLANTINGS | EA | EA | Number of plants | 180505 | |||
This includes the planting of trees, shrubs, and other vegetation for site beautification or improvement. | ||||||||
G205006 | PLANTERS | EA | EA | Number of planters | 180506 | |||
Planters are exterior decorative containers that contain plants or trees. | ||||||||
G205007 | IRRIGATION SYSTEMS | SY | M2 | Area of site to be watered | 180507 | |||
This includes the installation of underground irrigation systems required for watering of trees, shrubs, and grass or other vegetation. | ||||||||
G205090 | OTHER LANDSCAPING | XX | XX | 18059X | ||||
Landscaping not described by the assembly categories listed above. | ||||||||
G2060 | AIRFIELD PAVING | SY | M2 | Area of paving | ||||
Aircraft parking apron and runway paving. | ||||||||
G206001 | AIRFIELD PAVING CONSTRUCTION | SY | M2 | Area of paving | ||||
G206002 | OTHER PAVING | SY | M2 | Area of paving | ||||
G206003 | JOINTS AND ANCHORAGE | SY | M2 | Area of paving | ||||
G206004 | NAVIGATION AIDS | LS | LS | |||||
G206005 | AIRFIELD MARKINGS | LS | LS | |||||
G30 | SITE CIVIL/MECHANICAL UTILITIES | EA | EA | Each utility | ||||
Site mechanical utilities includes water supply, sanitary sewer, storm sewer, heating distribution, cooling distribution, fuel distribution, and other site mechanical utilities, such as industrial waste systems. | ||||||||
G3010 | WATER SUPPLY | LF | M | Length of system | 1901 | |||
This includes installation or construction of water distribution systems and facilities. | ||||||||
G301001 | WELL SYSTEMS | EA | EA | Each system | 190101 | |||
This includes all the components necessary to install a well, including drilling, installing casings, pumps, valves, etc. | ||||||||
G301002 | POTABLE WATER DISTRIBUTION | LF | M | Length of system | 190102 | |||
This includes construction and installation of underground piping, valve boxes, and valves. | ||||||||
G301003 | POTABLE WATER STORAGE | GAL | GAL | Amount stored | 190103 | |||
This includes construction and installation of tanks, both at grade and elevated. | ||||||||
G301004 | FIRE PROTECTION WATER DISTRIBUTION | LF | M | Length of system | 190104 | |||
This includes construction and installation of dedicated water piping for fire protection system only. This does not include potable water distribution systems that are used as a water source for fire protection systems. | ||||||||
G301005 | FIRE PROTECTION WATER STORAGE | GAL | GAL | Amount stored | 190105 | |||
This includes tanks on grade and elevated for storage of water for fire protection only. | ||||||||
G301006 | NON-POTABLE WATER DISTRIBUTION | LF | M | Length of system | 190106 | |||
This includes construction and installation of water distribution system not for consumption, such as irrigation or hydro-electric power generation and from reservoirs to treatment facilities. | ||||||||
G301007 | PUMPING STATIONS | GPM | L/S | Operating capacity | 190107 | |||
This includes construction and installation of pumps, valves, and piping. | ||||||||
G301008 | PACKAGED WATER TREATMENT PLANTS | GPD | GPD | Operating capacity | 190108 | |||
This includes installation of completely assembled water treatment plants. | ||||||||
G301090 | OTHER WATER SUPPLY | XX | XX | 19019X | ||||
Water supply not described by the assembly categories listed above. | ||||||||
G3020 | SANITARY SEWER | LF | M | Length of system | 1902 | |||
This includes all assemblies necessary for sewage collection systems. | ||||||||
G302001 | SANITARY SEWER PIPING | LF | M | Length of piping | 190201 | |||
This includes installation of piping for collection of sewage. | ||||||||
G302002 | SANITARY SEWER MANHOLES & CLEANOUTS | EA | EA | Each manhole or cleanout | 190202 | |||
This includes construction and installation of manholes and cleanouts in sewage collection systems. | ||||||||
G302003 | LIFT STATIONS AND PUMPING STATIONS | GPM | L/S | Operating capacity | 190203 | |||
This includes construction and installation of piping and equipment in lift stations. | ||||||||
G302004 | PACKAGED SANITARY SEWER TREATMENT PLANTS | GPD | L/S | Operating capacity | 190204 | |||
This includes installation of pre-assembled sewage treatment plants. | ||||||||
G302005 | SEPTIC TANKS | GAL | L | Volume of tank | 190205 | |||
This includes installation of prefabricated septic tanks or the construction of septic tanks. | ||||||||
G302006 | DRAIN FIELDS | LF | M | Length of field | 190206 | |||
This includes installation of drain fields for disposal of effluent from septic tanks. | ||||||||
G302090 | OTHER SANITARY SEWER | XX | XX | 19029X | ||||
Sanitary sewers not described by the assembly categories listed above. | ||||||||
G3030 | STORM SEWER | LF | M | Length of system | 1903 | |||
This includes construction of storm water collection systems. | ||||||||
G303001 | STORM SEWER PIPING | LF | M | Length of piping | 190301 | |||
This includes installation of piping for collection of storm water. | ||||||||
G303002 | STORM SEWER STRUCTURES | EA | EA | Each manhole or cleanout | ||||
This includes construction and installation of manholes for storm water collection systems. | ||||||||
G303003 | LIFT STATIONS | GPM | L/S | Operating capacity | 190303 | |||
This includes construction of lift stations including piping, pumps, and controls. | ||||||||
G303004 | CULVERTS | LF | M | Length of culvert | 190305 | |||
This includes construction and installation of culverts for storm water systems. | ||||||||
G303005 | HEADWALLS | EA | EA | Each structure | 190305 | |||
This includes construction of headwalls and installation of catch basins for storm water systems. | ||||||||
G303006 | EROSION & SEDIMENT CONTROL MEASURES | SY | M2 | Area to control | 190306 | |||
This includes construction to control erosion due to runoff. | ||||||||
G303007 | STORMWATER MANAGEMENT | GAL | GAL | Volume of collection area | ||||
G303090 | OTHER STORM SEWER | XX | XX | 19039X | ||||
Storm sewers not described by the assembly categories listed above. | ||||||||
G3040 | HEATING DISTRIBUTION | LF | M | Length of system | 1905 | |||
This includes overhead and underground hot water, steam, and condensate piping. | ||||||||
G304001 | OVERHEAD HOT WATER SYSTEMS | LF | M | Length of system | 190501 | |||
This includes installation of overhead hot water supply and return piping. | ||||||||
G304002 | OVERHEAD STEAM SYSTEMS | LF | M | Length of system | 190502 | |||
This includes installation of overhead steam supply and condensate return piping. | ||||||||
G304003 | UNDERGROUND HOT WATER SYSTEMS | LF | M | Length of system | 190503 | |||
This includes installation of underground hot water supply and return piping. | ||||||||
G304004 | UNDERGROUND STEAM DISTRIBUTION SYSTEMS | LF | M | Length of system | 190504 | |||
This includes installation of underground steam supply and condensate return piping. | ||||||||
G304005 | REINFORCED CONCRETE MANHOLES & VALVE BOXES | EA | EA | Each structure | ||||
This includes installation of prefabricated trench boxes for shoring during installation of piping. | ||||||||
G304006 | PUMPING STATIONS | EA | EA | Each pumping station | ||||
G304090 | OTHER HEATING DISTRIBUTION | XX | XX | 19059X | ||||
Heating distribution not described by the assembly categories listed above. | ||||||||
G3050 | COOLING DISTRIBUTION | LF | M | Length of system | 1906 | |||
This includes construction and installation of chilled water distribution systems. | ||||||||
G305001 | OVERHEAD COOLING SYSTEMS | LF | M | Length of system | 190601 | |||
This includes installation of overhead chilled water supply and return piping. | ||||||||
G305002 | UNDERGROUND COOLING SYSTEMS | LF | M | Length of system | 190602 | |||
This includes installation of underground chilled water supply and return piping. | ||||||||
G305003 | TRENCHBOXES | LF | M | Length of trench | 190603 | |||
This includes installation of prefabricated trench boxes for shoring during installation of piping. | ||||||||
G305004 | WELLS FOR COOLING | EA | EA | Each well | ||||
G305005 | PUMPING STATIONS | EA | EA | Each pumping station | ||||
G305006 | ON-SITE COOLING TOWERS | EA | EA | Each cooling tower | ||||
G305090 | OTHER COOLING DISTRIBUTION | XX | XX | 19069X | ||||
Cooling distribution not described by the assembly categories listed above. | ||||||||
G3060 | FUEL DISTRIBUTION | GAL | L | Volume of storage tank | 1908 | |||
This includes installation of piping and storage tanks for building and aviation fuels. | ||||||||
G306001 | LIQUID FUEL DISTRIBUTION PIPING SYSTEM | LF | M | Length of piping | 190801 | |||
This includes installation of piping for fuel and oil distribution. This includes equipment related to piping, system leak detection and tightness testing. | ||||||||
G306002 | AVIATION FUEL DISTRIBUTION PIPING SYSTEM | LF | M | Length of piping | 190801 | |||
This includes installation of piping for aviation fuel distribution and equipment related to the piping. This also includes system leak detection and tightness testing. | ||||||||
G306003 | LIQUID FUEL STORAGE TANKS | GAL | L | Volume of storage tank | 190802 | |||
This includes installation of buried or above ground fuel tanks relating to liquid fuel or aviation systems. | ||||||||
G306004 | LIQUID FUEL DISPENSING EQUIPMENT | EA | EA | Each piece of equipment | 190803 | |||
This includes equipment relating to liquid fuel and aviation systems. | ||||||||
G306005 | LIQUID FUEL SYSTEM TRENCHBOXES | LF | M | Length of trench | 190804 | |||
This includes installation of prefabricated trench boxes for shoring during installation of piping. | ||||||||
G306006 | GAS DISTRIBUTION PIPING (NATURAL AND PROPANE) | LF | M | Length of piping | ||||
This includes piping for distribution of natural or propane gas. | ||||||||
G306007 | GAS STORAGE TANKS | GAL | L | Volume of storage tank | ||||
This includes installation of tanks for natural or propane gas. | ||||||||
G306008 | GAS SYSTEM TRENCHBOXES | LF | M | Length of trench | ||||
This includes installation of prefabricated trench boxes for shoring during installation of piping. | ||||||||
G306009 | OTHER GAS DISTRIBUTION | XX | XX | |||||
Gas distribution not described by the assembly categories listed above. | ||||||||
G306090 | OTHER FUEL DISTRIBUTION | XX | XX | 19089X | ||||
Fuel not described by the assembly categories listed above. | ||||||||
G3090 | OTHER SITE MECHANICAL UTILITIES | LF | M | Length of system | 1904 | |||
This includes all systems for collection of contaminated waste requiring special treatment. | ||||||||
G309001 | INDUSTRIAL WASTE PIPE | LF | M | Length of piping | 190401 | |||
This includes construction and installation of all piping for collection of industrial waste. | ||||||||
G309002 | INDUSTRIAL WASTE MANHOLES & CLEANOUTS | EA | EA | Each manhole or cleanout | 190402 | |||
This includes construction of manholes and cleanouts for industrial waste. | ||||||||
G309003 | INDUSTRIAL WASTE LIFT STATIONS | GPM | L/S | Operating capacity | 190403 | |||
This includes construction and installation of industrial waste lift stations and equipment. | ||||||||
G309004 | INDUSTRIAL WASTE HOLDING TANKS & SEPARATORS | EA | EA | Number of tanks | 190404 | |||
This includes construction or installation of special tanks such as silver recovery tanks or separators such as oil water separators. | ||||||||
G309005 | INDUSTRIAL WASTE TRENCHBOXES | LF | M | Length of trench | 190405 | |||
This includes installation of prefabricated trench boxes for shoring during installation of piping. | ||||||||
G309090 | OTHER INDUSTRIAL WASTE | XX | XX | 19049X | ||||
Industrial waste not described by the assembly categories listed above, such as petroleum oil and lubricant distribution systems. | ||||||||
G40 | SITE ELECTRICAL UTILITIES | EA | EA | Systems total | 20 | |||
This system includes exterior electrical systems and equipment including substations, overhead and underground distribution systems, metering systems and equipment, exterior lighting, lightning protection systems, communication and alarm systems, and cathodic protection. | ||||||||
G4010 | ELECTRICAL DISTRIBUTION | KVA | KVA | Total rated capacity | ||||
Electrical distribution includes the following: substations; transformers; switches, controls and devices; overhead electric conductors; towers, poles, crossarms and insulators; underground electric conductors; ductbanks, manholes, handholes and raceways; grounding systems; and metering. | ||||||||
G401001 | SUBSTATIONS | KVA | KVA | Total rated capacity | 2001 | |||
This system includes substation equipment and materials required from the primary power source. | ||||||||
G401002 | TRANSFORMERS | KVA | KVA | Total rated capacity | 200101 | |||
Electrical power transformers used in conjunction with electrical substations. May include pole/tower or pad-mounted transformers located outside the building. | ||||||||
G401003 | SWITCHES, CONTROLS & DEVICES | EA | EA | Number of separate components | 200102 | |||
Includes all components of switchgear, voltage regulators and busbars used with electrical substations. | ||||||||
G401004 | OVERHEAD ELECTRIC CONDUCTORS | LF | M | Length of conductor | 200103 | |||
Includes conductors used in conjunction with substations. | ||||||||
G401005 | TOWERS, POLES, CROSSARMS & INSULATORS | EA | EA | Number of towers and poles | 200104 | |||
Towers, poles, crossarms, and insulators used in conjunction with substations. | ||||||||
G401006 | UNDERGROUND ELECTRIC CONDUCTORS | LF | M | Length of conductor | 200105 | |||
Includes conductors used in conjunction with substations. | ||||||||
G401007 | DUCTBANKS, MANHOLES, HANDHOLES & RACEWAYS | EA | EA | Number of ductbanks and access points | 200106 | |||
Components used in conjunction with electrical substations. | ||||||||
G401008 | GROUNDING SYSTEMS | EA | EA | Number of systems | 200108 | |||
Grounding systems used in conjunction with substations. Grounding systems for buildings, power distribution, and other electrical systems and subsystems are included with those other systems. | ||||||||
G401009 | METERING | EA | EA | Number of meters | 200208 | |||
Includes components used in conjunction with exterior electrical distribution. | ||||||||
G401010 | CATHODIC PROTECTION | EA | EA | Each system | ||||
Includes a system used in conjunction with exterior electrical distribution for corrosion control. | ||||||||
G401011 | EQUIPMENT REQUIREMENTS FOR COASTAL AND HIGH HUMIDITY AREAS | XX | XX | 0 | ||||
G401090 | OTHER ELECTRIC TRANSMISSION & DISTRIBUTION | XX | XX | 20019X | ||||
Substations not described by the assembly categories listed above. | ||||||||
G4020 | SITE LIGHTING | LF | M | Length of distribution | 2003 | |||
Exterior electrical lighting systems including conductors, switches, controls and other devices, supporting structures, grounding systems, and all other equipment required to support a lighting system. | ||||||||
G402001 | EXTERIOR LIGHTING FIXTURES & CONTROLS | EA | EA | Number of fixtures | 200301 | |||
Includes fixtures, controls, and all components used in conjunction with exterior lighting. | ||||||||
G402002 | SPECIAL SECURITY LIGHTING SYSTEMS | EA | EA | Number of systems | 200302 | |||
Includes all components used for special security lighting. | ||||||||
G402003 | OTHER AREA LIGHTING | EA | EA | Number of fixtures | 200303 | |||
Includes components and equipment used for area lighting. | ||||||||
G402004 | LIGHTING POLES | EA | EA | Number of towers and poles | 200304 | |||
Poles used to support lighting fixtures and support equipment. | ||||||||
G402005 | UNDERGROUND ELECTRIC CONDUCTORS | LF | M | Length of conductor | 200305 | |||
Includes conductors for underground electrical distribution to lighting systems. | ||||||||
G402006 | DUCTBANKS, MANHOLES & HANDHOLES | EA | EA | Number of ductbanks and access points | 200306 | |||
Includes all components used in conjunction with exterior lighting. | ||||||||
G402007 | GROUNDING SYSTEMS | EA | EA | Number of systems | 200307 | |||
Grounding systems used in conjunction with exterior lighting. | ||||||||
G4030 | SITE COMMUNICATION AND SECURITY | LF | M | Length of distribution | 2004 | |||
This system includes cables, ductbanks, manholes, and all other equipment required to support exterior communication and alarm systems. | ||||||||
G403001 | TELECOMMUNICATIONS SYSTEMS | LF | M | Length of distribution | 200401 | |||
Includes all components, cables, and equipment used in conjunction with exterior telephone systems. | ||||||||
G403002 | CABLE TV SYSTEMS (CATV) | LF | M | Length of distribution | 200404 | |||
Includes all components, cables, and equipment used in conjunction with exterior cable TV systems. | ||||||||
G403003 | CABLES & WIRING | LF | M | Length of conductor | 200501 | |||
Includes cables, wiring, and equipment used in conjunction with exterior security systems. | ||||||||
G403004 | DUCTBANKS, MANHOLES & HANDHOLES | EA | EA | Number of ductbanks and access points | 200502 | |||
Includes ductbank, manholes, and handholes used in conjunction with exterior security systems. | ||||||||
G403005 | TOWERS, POLES & STANDS | EA | EA | Number of towers, poles and stands | 200503 | |||
Includes towers, poles, stands, and equipment used in conjunction with exterior security systems. | ||||||||
G403006 | TV CAMERAS & MONITORS | EA | EA | Number of cameras and monitors | 200504 | |||
Includes cameras, monitors, and components used in conjunction with exterior security systems. | ||||||||
G403007 | ELECTRONIC SECURITY SYSTEMS (ESS) | EA | EA | Number of systems | 200505 | |||
Includes components and systems used in conjunction with exterior security systems. | ||||||||
G403008 | OTHER COMMUNICATION & ALARM | XX | XX | 180601 | ||||
Includes all components, cables, and equipment used in conjunction with other special communication and alarm systems not defined above. | ||||||||
G403009 | GROUNDING SYSTEMS | EA | EA | Number of systems | 200505 | |||
Includes grounding systems used in conjunction with exterior security systems. | ||||||||
G403090 | OTHER SECURITY SYSTEMS | XX | XX | 20059X | ||||
Includes all components and equipment used in conjunction with special security systems not defined above. | ||||||||
G4090 | OTHER SITE ELECTRICAL UTILITIES | LF | M | Length of conductor | ||||
This system includes alternate energy sources. This system also includes sacrificial anodes, induced current conductors, and components used in conjunction with cathodic protection. | ||||||||
G409001 | SACRIFICIAL ANODE CATHODIC PROTECTION SYSTEM | EA | EA | Number of anodes | 20601 | |||
Includes all components required in conjunction with sacrificial anode system. | ||||||||
G409002 | INDUCED CURRENT CATHODIC PROTECTION SYSTEM | LF | M | Length of conductor | 20602 | |||
Includes conductors and termination required for cathodic protection. | ||||||||
G409003 | EMERGENCY POWER GENERATION | KVA | KVA | Total rated capacity | ||||
G409090 | OTHER CATHODIC PROTECTION | XX | XX | 2069X | ||||
Includes components and equipment used in conjunction with other cathodic protection systems not defined above. | ||||||||
G90 | OTHER SITE CONSTRUCTION | LS | LS | |||||
Other site construction includes service and pedestrian tunnels, bridges, railroad spurs, and snow melting systems. | ||||||||
G9010 | SERVICE AND PEDESTRIAN TUNNELS | XX | XX | |||||
This assembly includes service and pedestrian tunnels. | ||||||||
G901001 | CONSTRUCTION OF SERVICE AND PEDESTRIAN TUNNELS | LF | M | Length of tunnel | ||||
This assembly includes construction of service and pedestrian tunnels. | ||||||||
G901002 | PREFABRICATED SERVICE AND PEDESTRIAN TUNNELS | LF | M | Length of tunnel | ||||
This assembly includes prefabricated service and pedestrian tunnels. | ||||||||
G9090 | OTHER SITE CONSTRUCTION | XX | XX | |||||
Other site construction includes bridges, railroad spurs and snow melting systems. | ||||||||
G909001 | BRIDGES | SY | M2 | Area of structure | 180601 | |||
Bridges included here are typically small spans or overpasses that are not meant to be used to estimate spans over large bodies of water. Options exist for cast-in-place concrete T-beam, precast I-beam, precast box, concrete and steel composite, laminated timber deck bridge structures. | ||||||||
G909002 | RAILROAD SPURS | LF | M | Length of track | 180602 | |||
Railroad assemblies exist for 110, 115, and 132 lb. tracks and ties. Turnouts, roadway crossings, derailleurs, stops, and bumpers are also included. | ||||||||
G909003 | SNOW MELTING SYSTEMS | EA | EA | Number of systems | ||||
G909090 | OTHER SPECIAL CONSTRUCTION | XX | XX | 18069X | ||||
Any special construction not covered in the above categories. |
Unf L1 | Unf L2 | Unf L3 | WBS L4 | Definition | E UOM | M UOM | Quantity Definition | WBS Ref No |
---|---|---|---|---|---|---|---|---|
H | WATERFRONT | |||||||
H10 | WATERFRONT STRUCTURES | LS | LS | |||||
Waterfront Structures including wharves, piers, dolphins, trestles, and other structures and appurtenances necessary for the safe mooring of vessels and to support waterfront operations. | ||||||||
H1010 | SUBSTRUCTURE | XX | XX | |||||
This assembly includes substructure components for waterfront structures, such as pile foundations, pile caps, quays, relieving platforms, revetments, seawalls, boat ramps, cut-off walls, firewalls, and hanging panels. | ||||||||
H101001 | PILE FOUNDATIONS | VLF | VM | Length of piles | ||||
H101002 | PILE CAPS | XX | XX | |||||
H101003 | QUAYS | XX | XX | |||||
H101004 | RELIEVING PLATFORMS | XX | XX | |||||
H101005 | REVETMENTS | XX | XX | |||||
H101006 | SEAWALLS | XX | XX | |||||
H101007 | BOAT RAMPS | XX | XX | |||||
H101008 | CUT-OFF WALLS | XX | XX | |||||
H101009 | FIREWALLS AND HANGING PANELS | XX | XX | |||||
H101090 | OTHER SUBSTRUCTURE COMPONENTS | XX | XX | |||||
H1020 | SUPERSTRUCTURE | XX | XX | |||||
This assembly includes superstructure components for waterfront structures, such as beams and girders, columns, utility enclosures, and other features that support the operation deck area. | ||||||||
H102001 | BEAMS AND GIRDERS | XX | XX | |||||
H102002 | COLUMNS | XX | XX | |||||
H102003 | UTILITY ENCLOSURES | XX | XX | |||||
H102090 | OTHER SUPERSTRUCTURE ELEMENTS | XX | XX | |||||
H1030 | DECK | XX | XX | |||||
This assembly includes the components for the deck, including elevated deck, on-grade deck, deck overlays, curbs and bullrails, mooring hardware foundation, high mast lighting foundations, utility mounds, expansion joints, guard post and railings, paint striping and other related features. | ||||||||
H103001 | DECK | XX | XX | |||||
H103002 | ON-GRADE SLAB | XX | XX | |||||
H103003 | DECK OVERLAY | XX | XX | |||||
H103004 | CURBS AND BULLRAILS | XX | XX | |||||
H103005 | MOORING FOUNDATIONS | XX | XX | |||||
H103006 | HIGH MAST LIGHTING FOUNDATIONS | XX | XX | |||||
H103007 | UTILITY MOUNDS | XX | XX | |||||
H103008 | EXPANSION JOINTS | XX | XX | |||||
H103009 | GUARD POSTS AND RAILING | XX | XX | |||||
H103010 | PAINT STRIPING | XX | XX | |||||
H103090 | OTHER DECK COMPONENTS | XX | XX | |||||
H1040 | MOORING AND BERTHING SYSTEM | XX | XX | |||||
This assembly includes the components for the mooring hardware and fendering systems, including foundations, anchor bolts, and support systems. | ||||||||
H104001 | PRIMARY FENDER SYSTEM | XX | XX | |||||
H104002 | SECONDARY FENDER SYSTEM | XX | XX | |||||
H104003 | CORNER FENDER SYSTEM | XX | XX | |||||
H104004 | DOLPHINS | XX | XX | |||||
H104005 | MOORING HARDWARE | XX | XX | |||||
H104090 | OTHER MOORING AND BERTHING COMPONENTS | XX | XX | |||||
H1050 | APPURTENANCES | LS | LS | |||||
This assembly includes the appurtenances such as handrails, brows, cable booms, floats, safety ladders, life rings, oil containment booms, and other similar features. | ||||||||
H20 | GRAVING DRYDOCKS | LS | LS | |||||
H30 | COASTAL PROTECTION | LS | LS | |||||
Coastal Protection System consists of all waterfront breakwaters, wave protection armor, slope protection, revetments, and other features necessary and required for the protection of waterfront facilities from damage by wave, tide and current. | ||||||||
H3010 | WAVE PROTECTION | XX | XX | |||||
This assembly includes required wave protection features, such as breakwaters, wave protection armor for slope protection, revetment and scour protection. | ||||||||
H301001 | WAVE PROTECTION ARMORS | XX | XX | |||||
H301002 | BREAKWATERS | XX | XX | |||||
H3020 | SLOPE PROTECTION | XX | XX | |||||
This assembly includes required slope protection features, such as revetment or embankment dikes. | ||||||||
H302001 | ROCK REVETMENTS | XX | XX | |||||
H302002 | GRANULAR FILL REVETMENTS | XX | XX | |||||
H302003 | COMBINED ROCK AND GRANULAR FILL REVETMENTS | XX | XX | |||||
H40 | NAVIGATION DREDGING AND RECLAMATION | LS | LS | |||||
Navigation Dredging and Reclamation System consists of all dredging of navigation channels, approaches, turning basins, and berthing areas near piers, wharves, dolphins, and reclamation as necessary to navigate the vessels to the berths and produce reclaimed land to support construction of the waterfront facilities. | ||||||||
H4010 | DREDGING | XX | XX | |||||
H4020 | DREDGING DISPOSAL | XX | XX | |||||
H402001 | OCEAN DISPOSAL | XX | XX | |||||
H402002 | NEW CONFINED DISPOSAL FACILITIES | XX | XX | |||||
H402003 | EXISTING CONFINED DISPOSAL FACILITIES | XX | XX | |||||
H4030 | RECLAMATION | XX | XX | |||||
H50 | WATERFRONT UTILITIES | LS | LS | |||||
The Waterfront Utility System consists of civil/mechanical utilities, electrical utilities, and fire protection to be installed on waterfront structures | ||||||||
H5010 | CIVIL/MECHANICAL UTILITIES | XX | XX | |||||
H501001 | POTABLE WATER | XX | XX | |||||
H501002 | SALTWATER | XX | XX | |||||
H501003 | SANITARY SEWER | XX | XX | |||||
H501004 | BILGE AND OILY WASTE | XX | XX | |||||
H501005 | STEAM | XX | XX | |||||
H501006 | COMPRESSED AIR | XX | XX | |||||
H501090 | OTHER CIVIL/MECHANICAL UTILITIES | XX | XX | |||||
H501091 | MISCELLANEOUS MATERIAL | XX | XX | |||||
H5020 | ELECTRICAL UTILITIES | XX | XX | |||||
H502001 | POWER DISTRIBUTION SYSTEM | XX | XX | |||||
H502002 | TELECOMMUNICATION SYSTEM | XX | XX | |||||
H502003 | LIGHTING SYSTEMS | XX | XX | |||||
H502004 | LIGHTNING PROTECTION SYSTEM | XX | XX | |||||
H502005 | POWER BOOMS | XX | XX | |||||
H502090 | OTHER ELECTRICAL UTILITIES | XX | XX | |||||
H5030 | WATERFRONT FIRE PROTECTION | XX | XX | |||||
H503001 | FIRE PROTECTION WATER DISTRIBUTION SYSTEM | XX | XX | |||||
H503002 | FIRE ALARM | XX | XX | |||||
H60 | WATERFRONT DEMOLITION | LS | LS | |||||
H6010 | IN OR OVER-WATER DEMOLITION | XX | XX | |||||
H6020 | NON IN OR OVER-WATER DEMOLITION | XX | XX | |||||
H6030 | HAZARDOUS COMPONENTS ABATEMENT | XX | XX | |||||
H70 | WATERFRONT ATFP | LS | LS | |||||
H7010 | WATERSIDE ATFP | XX | XX | |||||
H7020 | LANDSIDE ATFP | XX | XX |
Unf L1 | Unf L2 | Unf L3 | WBS L4 | Definition | E UOM | M UOM | Quantity Definition | WBS Ref No |
---|---|---|---|---|---|---|---|---|
Z | GENERAL | LS | LS | |||||
The common or general requirements from the Performance Technical Specification Sections. |
Federal Facility Criteria: