Publish Date
Summary

vertical collage

This retrofit converts an existing constant volume multizone HVAC system (MZ–CV) to a variable volume (MZ–VV) system for increased energy efficiency. The technique makes limited changes in instrumentation and uses a novel control scheme to reduce fan speed and coil use when not needed. A demand controlled ventilation option also reduces ventilation when spaces are unoccupied. The retrofit is significantly less expensive and less disruptive than a full system change-out (to VAV). This retrofit can be an interim solution to meet energy reduction targets and accrue savings now while postponing large capital investment. Field demonstration found 24–60% energy savings at the air handler. Typical applications are expected to pay back in 3–5 yrs.

A suite of design and implementation support tools steps a potential user through technology evaluation, procurement, and performance verification. The files are numbered roughly in the probable order of use. Pertinent document formats (including PDF , Excel spreadsheet , Word document , PowerPoint , and AutoCAD drawing files (zipped) ) allow rapid system analyses and development of procurement packages.

Title

Date

View

01- Multizone to Variable Volume Overview Fact Sheet

02-17-2022

PDF

02- Multizone to Variable Volume Technical Note

04-14-2022

PDF

03- Multizone to Variable Volume Savings Estimator

08-01-2022

XLSX

04- Multizone to Variable Volume Pitch Briefing

04-07-2022

PPTX

05- Multizone to Variable Volume Scoping Guide

04-05-2022

XLSX

06- Multizone to Variable Volume Design Guide with Performance Work Statement, Specifications Book, and Sequences of Operation

10-03-2022

DOCX

07- Multizone to Variable Volume Points Schedules

02-15-2022

XLSX

08.1- Multizone to Variable Volume Bypass Unit Controls Drawings

02-14-2022

PDF

08.2- Multizone to Variable Volume Conventional Unit Controls Drawings

02-14-2022

PDF

08.3- Multizone to Variable Volume Neutral Deck Unit Controls Drawings

02-14-2022

PDF

09- Multizone to Variable Volume Commissioning Guide

04-05-2022

XLSX

10.1- Multizone to Variable Volume Bypass Unit AutoCAD Drawings (12 files)

02-14-2022

DWG/ZIP

10.2- Multizone to Variable Volume Conventional Unit AutoCAD Drawings (12 files)

02-14-2022

DWG/ZIP

10.3- Multizone to Variable Volume Neutral Deck Unit AutoCAD Drawings (12 files)

02-14-2022

DWG/ZIP

11- Exploring a Multizone To Variable Volume HVAC Controls Retrofit

09-01-2022

PDF

A technology field demonstration was conducted, and these design and implementation technology transfer tools were developed by the Engineer Research and Development Center, Construction Engineering Research Laboratory (ERDC-CERL) under the DoD Environmental Security Technology Certification Program (ESTCP).