Sustainable Laboratory Design

by Daniel Watch and Deepa Tolat
Perkins + Will

Last updated: 06-18-2010

Introduction

A typical laboratory currently uses five times as much energy and water per square foot as a typical office building. Research facilities are so energy demanding for a variety of reasons:

  • They contain large numbers of containment and exhaust devices;
  • They house a great deal of heat-generating equipment;
  • Scientists require 24-hour access; and
  • Irreplaceable experiments require fail-safe redundant backup systems and uninterrupted power supply (UPS) or emergency power.

In addition, research facilities have intensive ventilation requirements—including "once through" air—and must meet other health and safety codes, which add to energy use. Examining energy and water requirements from a holistic perspective, however, can identify significant opportunities for improving efficiencies while meeting or exceeding health and safety standards. Sustainable design of lab environments should also improve comfort and worker productivity.

Photo of EPA Campus-Research Triangle Park, NC (Lake view)Photo of EPA Campus-Research Triangle Park, NC

The EPA Campus at Research Triangle Park, North Carolina, which includes laboratory and administrative facilities, showcases flexible lab planning concepts incorporated with sustainable features such as daylighting, high-efficiency lighting, green building materials, and comprehensive construction waste recycling to create facilities that balance concerns related to cost, function, and the environment.
(Courtesy of HOK)

Description

The key aspects of sustainable laboratory design include:

  • Increased energy and water conservation and efficiency
  • Reduction or elimination of harmful substances and waste
  • Improvements to the interior and exterior environments, leading to increased productivity
  • Efficient use of materials and resources
  • Recycling and increased use of products with recycled content

See WBDG Sustainable Branch for more details on the principles of sustainable design.

The following table is an example of a sustainable design criteria chart set up for a specific laboratory project. Each criterion must be reviewed for each specific project.

Sustainable Design Criteria
ParameterCode MinimumCode ReferenceStandard PracticeDesign Target
Ventilation10 cfm/personASHRAE 62/89SameMaximize outdoor air in the breathing zone
Filtrationnone 35-80%65% pre filter
85% final filter
Indoor Design Temperature75° F summer
72° winter
 Same 
Humidity Controluncontrolled uncontrolled60% RH summer
40% RH winter
Equipment Heat DissipationNA 3-4W/sf1.5W/sf or 2W/sf with 75% diversity factor
Toilet Exhaust50 cfm/fixtureASHRAE 62/89Same2 cfm/sf
Connected Lighting Heat LoadNA 2W/sf0.5-0.75W/sf
Total task/ambient with occupancy sensors and daylight sensors
Lighting Levels100 ft. candles all direct Same20-30 ft. candles with ambient and task lighting
Building Shell Infiltration6"/100 sfASHRAE guideline3"/100 sf1.5"/100 sf
(Canadian Standard)
Building Shell Infiltration (alternate)0.60 cfm/sfASHRAE guideline0.30 cfm/sf0.10 cfm/sf
Exterior Wall InsulationU = 0.28 btu/sf-hr- FBOCA Energy Code0.10 btu/sf-hr- FU = 0.15 btu/sf-hr South
U = 0.05 btu/sf-hr (N, E, W)
Exterior Wall Moisture Controlnone  AIB - with insulation both sides
Roof InsulationU - 0.07 btu/sf-hrBOCA Energy CodeU - 0.05 btu/sf-hr- FU - 0.05 btu/sf-hr- F with low albedo surfacing
Windows    
  Glazing typeSingle/clear Double/clearheat reflecting clear
  Visible transmittance0.80 0.780.70
  Shading Coefficient1.00 0.800.43
  U value1.04 0.480.30
Heat Degree Days6,155 btuASHRAESameDetermined by DOE-2 or other energy analysis of TMY data

A. Architectural Considerations

The design of the building envelope—including overhangs, glazing, insulation, and (possibly) the use of photovoltaic panels—plays a large role in the research facility's energy efficiency.

Overhangs

Photo of NREL's Solar Energy Research Facility

The stepped design at NREL's Solar Energy Research Facility provides overhangs and light shelves to shade and direct natural light into the office spaces inside.

Overhangs for shading windows are often designed as part of the wall system to improve the quality of the natural light entering the interior space. The south elevation should have a horizontal overhang; east and west elevations usually require both horizontal and vertical overhangs. See also WBDG Sun Control and Shading Devices.

Glazing

The glazing material for exterior windows should have a thermal break and an insulating section between the inner and outer sections of the frames. Wood or fiberglass frames will give much better thermal performance than aluminum. Low-E windows with at least an R-3 insulation value should be used. "Superwindows" that incorporate multiple thin plastic films can have an R value as high as 12. The problem is that such windows cost up to four times as much as low-E glass. Operable windows generally will not reduce energy costs; in fact, they may increase energy usage, but they usually enhance the quality of the indoor environment and are therefore preferred by most clients. See also WBDG Windows and Glazing.

Roofs and Walls

The use of light-colored roofing with a high-albedo coating to reflect light and heat is recommended. The amount of wall and roof insulation needed will vary depending on the climate and the type of lab. For example, equipment-intensive labs will generate a lot of heat and in certain parts of the country will not require as much roof insulation as elsewhere. All electrical outlets and all plumbing and wire penetrations into the building should be sealed, since air leakage can be a significant source of energy waste as well as moisture problems in some parts of the country.

Today, there is quite a bit of discussion about using photovoltaic panels both to enclose a building and to generate electricity. Photovoltaic panels can be integrated into the building envelope as metal roofing, spandrel glazing, or semi-transparent vision glazing. See WBDG Building Integrated Photovoltaics (BIPV) But the panels are difficult to justify in traditional applications because the electricity they generate can cost more than electricity purchased from the grid.

B. Engineering Considerations

Sustainable engineering addresses civil engineering concerns as well as the design of mechanical, plumbing, and lighting systems. First and foremost, the design team and client should contact the local utility company to explore opportunities for rebates to assist in the purchase of high-efficiency equipment or the implementation of other energy conservation measures.

Civil Engineering

Civil engineering issues to consider include the use of pervious materials and light colored wherever possible. In preparing a site for new construction, designers should consider transplanting existing trees instead of removing them. Proper storm water management strategies are also important to reduce erosion and replenish local aquifers. See also WBDG Sustainable—Optimize Site Potential and Achieving Sustainable Site Design through Low Impact Development Practices.

Mechanical, Plumbing, and Water Conservation Strategies

For the HVAC system, it is most important to simulate the operation of the whole system and to analyze assumptions using whole-building systems analysis software such as DOE-2. See also Laboratories for the 21st Century: Energy Analysis (PDF 1.6 MB, 82 pgs). Reducing building loads is critical to improving energy efficiency, and one key way to reduce loads is to reduce the amount of outside air used for ventilation. This raises a design challenge, however, since air supplied to laboratories is exposed to chemical contaminants and therefore cannot be returned to the central air handling system and must be exhausted. The volume of ventilation air required for the laboratories is typically greater than that for classrooms, lecture halls, and offices. One strategy to utilize outside air efficiently is to install a mechanical unit that introduces 100 percent outside air into classrooms and lecture halls. Return air from these areas is reconditioned through the mechanical system and then ducted to the laboratories as supply air. The supply air to the laboratories is exhausted. In this way, the outside air is used twice before being exhausted. Note that this strategy may reduce the ability to transform classrooms into lab spaces in the future.

Photo of Louis Stoke Laboratories' Building 50-Bethesda, MDPhoto of Desiccant energy recovery wheel used at the Louis Stoke Laboratories' Building 50-Bethesda, MD

The desiccant energy recovery wheel shown here is just one of the energy-efficient features used at the Louis Stoke Laboratories' Building 50. It is estimated that the facility will require 40% less energy than a traditional research laboratory—Bethesda, MD

Electronic air cleaners help minimize air resistance from filters. Maintenance is also important. Effective filter-replacement schedules help keep indoor air quality high and conserve energy. Control systems for variable speed drives on pumps, fans, and compressors should be used only if the controls will be regularly maintained and calibrated.

Photo of The Fred Hutchinson Cancer Research Center-Seattle, WA

The Fred Hutchinson Cancer Research Center in Seattle, WA was retrofitted to reduce sterilizer water use and water waste, resulting in an annual saving of 10,000 gallons of water.

Numerous strategies can be employed for improving the energy efficiency of cooling, heating, and plumbing systems:

  • Insulate hot water, steam, and chilled water piping.
  • Maintain condenser water as cool as possible, but not less than 20 degrees above chilled water supply temperature.
  • Reuse wasted heat with a heat recovery system.
  • Install an economizer at the boiler. (The water-side economizer will help with humidity controls.)
  • Maintain hot water for washing hands at 105 degrees F. Consider using local hot water tanks at kitchens, restrooms, and other areas instead of central hot water.
  • For plumbing systems, consider using ultra-low-flow toilets (0.5 gallons per flush), waterless urinals, dual flush toilets, ultra-low-flow lavatory faucets, and automated controls such as infrared sensors for faucets.
  • Harvesting rainwater and reusing "gray water" from sinks for irrigation may help reduce water costs.

See also WBDG—High Performance HVAC.

Sustainable Lighting Design

Sustainable lighting design reduces energy use while enhancing employee comfort and productivity. Sustainable lighting strategies include the use of compact fluorescents (CFLs) rather than incandescent lamps, maximizing natural daylighting throughout a facility, and employing various photosensing technologies to conserve energy.

Incandescent lamps are extremely inefficient, energy-wise, using only 10 percent of the energy they consume to produce light (the rest is given off as heat). CFLs should be used instead. Research office lighting can be less than 0.75 watts/sf. connected load, and with lighting controls it may consume less than 0.5 watts/sf. Where functional requirements permit, lighting design should combine task and ambient lighting to reduce the high overall light levels. Good task lighting lessens glare and eyestrain. See also WBDG Energy Efficient Lighting.

Daylighting

Illustration of lab interior

Maximizing the availability of natural daylight is an important principle of sustainable design. Not only does it reduce energy use, but it also increases comfort and enhances productivity. Designers should strive to direct natural light into most laboratory spaces and public areas so that, from almost anywhere in the building, people have the opportunity to look outdoors to see what the weather is like and orient themselves to the time of day. Wherever possible, daylighting should be the primary source of illumination; artificial lighting should be thought of as a supplement to, rather than a replacement for, daylighting.

Typically, the first 15 feet of depth at the perimeter of the building can be entirely lit by daylight during the daytime. The use of light shelves can extend the daylight zone as far as 45 feet into the building. Clerestory windows and skylights can be used to get even more natural daylight into the building. See also WBDG Daylighting.

Daylighting control systems determine the amount of light available in a given space and switch off one or more banks of lights whenever there is enough sunlight. Both full-range and step fluorescent dimming systems work well.

Lighting Controls

Photo of Nidus Center for Scientific Enterprise-St. Louis, MO

Nidus Center for Scientific Enterprise, a 41,000-sf plant and life sciences business incubator located on Monsanto's Creve Coeur research campus, features daylighting and lighting controls for energy efficiency and occupant comfort. A 30% reduction in energy use was achieved compared to what could have been expected from a conventional lab building—despite 24-hour per day lab use—St. Louis, MO.
(Courtesy of HOK)

A key principle to remember in regard to lighting control systems is "simpler is better." Some systems employ photosensing technologies. Photosensing devices can control off-on for exterior lights, triggering fixtures to add light to a particular area when light levels decline. Also, a number of new fluorescent and metal halide fixtures are available that employ daylight harvesting—storing solar energy in the fixture during daylight hours and then using that energy to run the lamp when daylight diminishes; outdoor lighting systems can easily be retrofitted for these fixtures.

Other photosensing technologies include programmable low-voltage control systems and occupancy sensors. The programmable low-voltage systems can control individual areas of the building or an entire building with one switch. These systems interface with the building automation and dimming systems. They are flexible, can easily accommodate building changes, have a local override capability, and can be used for large or small systems.

Occupancy sensors typically have a one-to-two-year payback. The sensors are designed with adjustable sensitivity levels and timing. There are two technologies: passive infrared and ultrasonic. Passive infrared sensors detect movement of heat between zones. They must have "a line of sight" to detect people in the lab. Ultrasonic occupancy sensors work by broadcasting ultrasonic sound waves, analyzing the returning waves and detecting movement through Doppler shifts. They are effective for larger rooms and can cover a 360-degree area. One problem is that air turbulence can trigger their operation. All occupancy sensor systems must be designed correctly to avoid nuisance operation. See also WBDG Electric Lighting Controls.

C. Other Sustainability Issues

"Green" Products

Some casework products now being manufactured are considered "green." Examples include hardwood, veneer, and plywood products that originate from certified sustainable forests. Steel products can also be "green"—for example, steel laboratory casework and fume hoods made of sheet metal that contains 20 to 25 percent scrap steel. (Sixty percent of the scrap steel comes from old cars and appliances, the other 40 percent from manufacturing fall-off.) There is one problem with recycled steel's "greenness," however: recycling steel is highly energy-intensive, which raises the question whether energy conservation or resource conservation is the better environmental/sustainable strategy. See also WBDG Sustainable—Use Environmentally Preferable Products and Using LEED on Lab Products.

Other Issues

Other sustainable design issues include direct digital control energy management systems, and commissioning the entire building to ensure that building systems are operating as efficiently as possible.

Buildings should be designed with long-term flexibility options, such as the lab module for all architectural and engineering systems, easy connects and disconnects to the engineering systems, and flexible casework. Computers that turn themselves off during non-working hours reduce energy use and cost by reducing cooling loads and electrical demands. Laptop computers use one-tenth the energy of desktop PCs.

Clients are pushing project design teams to create research laboratories that are responsive to current and future needs; that encourage interaction among scientists from various disciplines; that help recruit and retain qualified scientists; and that facilitates partnerships and development. As such, a separate WBDG Resource Page on Trends in Laboratory Design has been developed to elaborate on this emerging model of laboratory design.

D. Conclusion

All the architectural, engineering, and other sustainability issues should be studied on a project-by-project basis. Factors such as the client's specific goals, the type of lab being designed, the part of the country where the lab is located, and its position on the site will lead to different solutions. See also "Whole Buildings" Design Approach.

The U.S. Environmental Protection Agency (EPA) and the U.S. Department of Energy (DOE) have launched a new, voluntary program to improve the environmental performance of U.S. laboratories called the Laboratories for the 21st Century (Labs21) initiative. Labs21 is designed to improve laboratory energy and water efficiency, encourage the use of renewable energy sources, and promote environmental stewardship. Also available is the Labs21 Environmental Performance Criteria (EPC), a rating system specifically designed to assess the environmental performance of research facilities.

Application

Representative Examples

Numerous facilities have implemented high-performance design features into new or retrofit laboratory projects. Labs21 has developed the following case studies:

  • Fred Hutchinson Cancer Research Center
  • Lawrence Berkeley National Laboratory In-House Energy Management Program
  • National Institutes of Health (NIH) Louis Stokes Laboratories-Building 50
  • Nidus Center for Scientific Enterprise, St. Louis, MO
  • Pharmacia Corporation Pharmacia Building Q
  • Sandia National Laboratories Process and Environmental Technology Laboratory (PETL)
  • State of Georgia, Dept. of Public Health Georgia Public Health Laboratory
  • U.S. Environmental Protection Agency, National Vehicle and Fuel Emissions Laboratory

Relevant Codes and Standards

Federal Mandates

The following agencies and organizations have developed codes and standards affecting the design of research laboratories. Note that the codes and standards are minimum requirements. Architects, engineers, and consultants should consider exceeding the applicable requirements whenever possible.

Additional Resources

WBDG

Building / Space Types

Office Building, Research Facilities, Animal Research Facility, Research Laboratory, Academic Laboratory, Government Laboratory, Private Sector Laboratory, Laboratory: Dry, Laboratory: Wet

Design Objectives

Accessible, Aesthetics, Cost-Effective, Functional / Operational, Productive, Secure / Safe, Sustainable

Products and Systems

Federal Green Construction Guide for Specifiers

Project Management

Building Commissioning

Tools

LEED® Version 2.1 Credit / WBDG Resource Page Matrix, LEED®-DoD Antiterrorism Standards Tool

Publications

Organizations

Others