8.1 Electrical Engineering

Click the cells below to choose a level of standard for each attribute. Show Tooltips

IN THIS SECTION:  Transformers  |  Variable Frequency Drives  |  Metering  |  Building Automation System - Interface from Electrical Systems
Interior Electrical Distribution  |  Arc- Flash Reduction Maintenance Switches (ARMS) and Arc Flash Barriers  |  Surge Protection Devices
Lightning Protection Systems (LPS)  |  Grounding  |  Uninteruptible Power Systems (ABS)

AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Transformers
Efficiencies for Network Transformers and Substation Transformers (<= 600V Secondary & <=34.5 KV Primary)NEMA TP-1-200210% less losses than NEMA TP-1-200220% less losses than NEMA TP-1 -200225% less losses than NEMA TP-1-2002YesSubmit certified performance data for each unitNEMA TP-1 -2002Describe transformer efficiency requirements.Verify submittals and certified performance data from manufacturer for supplied transformer units to verify compliance.
Insulating fluid for oil-filled Network Transformers and Substation Transformers (<= 600V Secondary & <=34.5 KV Primary)65 C° non-petroleum-based insulating-oil65 C° non-petroleum-based insulating-oil65 C° FR3 non-petroleum-based insulating-oil65 C° FR3 non-petroleum-based insulating-oilYesNEMA TP-1-2002Describe transformer insulating fluid requirements.Verify submittals and certified performance data from manufacturer for supplied transformer units to verify compliance.
Efficiencies for Low-voltage Distribution Transformers (120/208 3Ph, 4W Secondary; 480V, 3Ph, 3W Primary)NEMA TP-1-200210 Percent less losses than NEMA TP-1 -200220 Percent less losses than NEMA TP-1 -200225 Percent less losses than NEMA TP-1 -2002Certified Representative Factory Test ReportNEMA TP-1-2002Describe low voltage distribution transformer efficiencies.Verify submittals and certified performance data from manufacturer for supplied transformer units to verify compliance.
Impedance for Low-voltage Distribution Transformers (120/208 3Ph, 4W Secondary; 480V, 3Ph, 3W Primary)>4 %Z>4 %Z>4 %Z>5 %ZCertified Representative Factory Test ReportNEMA TP-1-2002Describe transformer impedence requirements.Verify submittals and certified performance data from manufacturer for supplied transformer units to verify compliance.
Harmonic Rated Transformers & Harmonic Mitigating TransformersK-13 w/200% neutral
>4% Z
K-20 w/200% neutral
>4% Z
Zig-Zag 3rd Harmonic Mitigating Transformers (0 degree, and 30 degree), Copper windings, >4% Z, K13 (Match 0 and 30 degree transformers in distribution for harmonic mitigation of 5th and 7th order harmonics)Zig-Zag 3rd Harmonic Mitigating Transformers (0 degree, 15 degree and 30 degree), Copper windings, >4% Z, K13 (Match 0, 15 and 30 degree transformers in distribution for harmonic mitigation of 5th and 7th order harmonics)Certified Representative Factory Test ReportNEMA TP-1-2002Describe transformer harmonic requirements.Verify submittals and certified performance data from manufacturer for supplied transformer units to verify compliance.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Variable Frequency Drives
Use on motors 5HP (3.7kW) to 25 Hp (18.7kW)6-pulse width modulation (PWM) IGBT Drives6-pulse width modulation (PWM) IGBT Drives Passive Harmonic Filtration <5% THD Current at Drive Terminals6-pulse width modulation (PWM) IGBT Drives Active Harmonic Filtration <5% THD Current at Drive Terminals6-pulse width modulation (PWM) IGBT Drives IGBT Front End <5% THD Current at Drive Terminals >95% Input Power FactorIEEE 519 5% Current THD at Drive Input Terminals, IEEE 519 3% Voltage THD in at Sensitive Equipment Panels, and 5% Voltage THD at 480/277 Transformer Secondary TerminalsDescribe VFD requirements to show compliance with metrics.Verify submittals and certified performance data from manufacturer for supplied VFD's s to verify compliance.
Use on motors 30HP (22.4kW) to 100HP (74.6 kW)6-pulse width modulation (PWM) IGBT Drives. Provide 12 or 18 pulse where the harmonic analysis indicates noncompliance12-pulse width modulation IGBT Drives with integral input phase shifting transformers (PWM) <= 5% THD Current at Drive Terminals18-pulse width modulation IGBT Drives with integral input phase shifting transformers (PWM) <= 5% THD Current at Drive Terminals18-pulse width modulation IGBT Drives with integral input phase shifting transformers (PWM) <= 5% THD Current at Drive TerminalsIEEE 519 5% Current THD at Drive Input Terminals, IEEE 519 3% Voltage THD in at Sensitive Equipment Panels, and 5% Voltage THD at 480/277 Transformer Secondary TerminalsDescribe VFD requirements to show compliance with metrics.Verify submittals and certified performance data from manufacturer for supplied VFD's s to verify compliance.
Use on motors 125HP (93.3kW) and larger18-pulse width modulation IGBT Drives with integral input phase shifting transformers (PWM) <= 5% THD Current at Drive Terminals18-pulse width modulation IGBT Drives with integral input phase shifting transformers (PWM) <= 5% THD Current at Drive Terminals18-pulse width modulation IGBT Drives with integral input phase shifting transformers (PWM) <= 5% THD Current at Drive Terminals18-pulse width modulation IGBT Drives with integral input phase shifting transformers (PWM) <= 5% THD Current at Drive TerminalsIEEE 519 5% Current THD at Drive Input Terminals, IEEE 519 3% Voltage THD in at Sensitive Equipment Panels, and 5% Voltage THD at 480/277 Transformer Secondary TerminalsDescribe VFD requirements to show compliance with metrics.Verify submittals and certified performance data from manufacturer for supplied VFD's s to verify compliance.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Metering
Metering at Building MainsVoltmeter reading all phase to phase and phase to neutral voltages. Switchable ammeter and three-phase totalizing watt-hour meter. The power meter should be pulse-type and digital networked and/or tied into the Advanced Metering System.Utility Class 0.2%, (Phase Volts, Phase Currents, Neutral Currents, Ground Currents, power consumption KWH, adjustable power demand KW, KVA & KVAR, Power Factor)Utility Class 0.2% (Phase Volts, Phase Currents, Neutral Currents, Ground Currents, power consumption KWH, adjustable power demand KW,KVA & KVAR, Power Factor), Harmonic Waveform AnalysisUtility Class 0.2% (Phase Volts, Phase Currents, Neutral Currents, Ground Currents, power consumption KWH, power demand KVA & KVAR, Power Factor), Harmonic Waveform Analysis, and Transient Disturbance Monitoring for capture, remote alarm monitoring and disturbance download to laptopYesYesANSI C12.1 & C12.20Describe building electrical meter requirements and show on single line diagram.Verify submittals and supplied meter specifications to verify compliance.
Metering for Building FeedersAs required for Advanced Building Metering and ControlAs required for Advanced Building Metering and Control and to coordinate with ECMs for M&V (KW, KVA Demand, KWH)As required for Advanced Building Metering and Control and to coordinate with ECMs for M&V (KW, KVA Demand, KWH)As required for Advanced Building Metering and Control and to coordinate with ECMs for M&V (KW, KVA Demand, KWH)YesDescribe building electrical sub-metering requirements and show on single line diagram.Verify submittals and supplied meter specifications to verify compliance.
Metering TrendingAs required for Advanced Building Metering and ControlAs required for Advanced Building Metering and Control and with trending configured to coordinate with ECMs for M&V (KW, KVA Demand, KWH)As required for Advanced Building Metering and Control and with trending configured to coordinate with ECMs for M&V (KW, KVA Demand, KWH)As required for Advanced Building Metering and Control and with trending configured to coordinate with ECMs for M&V (KW, KVA Demand, KWH)YesDescribe electrical metering scheme and trend requirements.Verify submittals and supplied meter specifications to verify compliance.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Building Automation System - Interface from Electrical Systems
Electrical Meters input to BAS and graphic displays MODBUS / TCP / IP Protocol Meters / BACnet / LonWorks protocol Meters to match BAS with twisted pair to BAS for monitoring. The power meter should be networked and/or tied into the Advanced Metering System.MODBUS / TCP / IP / BACnet / LonWorks Protocol Meters to match BAS with twisted pair to BAS for monitoring and graphics. Interfaced to BAS and configured for Advanced Metering System. Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.MODBUS / TCP / IP / BACnet / LonWorks Protocol Meters to match BAS with twisted pair to BAS for monitoring and graphics (also ethernet for TCP/IP for metering customized graphical GUI at BAS front end)MODBUS / TCP / IP / BACnet / LonWorks Protocol Meters to match BAS with twisted pair to BAS for monitoring and graphics (also ethernet for TCP/IP for metering customized graphical GUI at BAS front end) and Wireless SubmetersYesYesANSI C12.1 & C12.20; EPACT 2005, EISA 2007 - Section 434(b)Describe meter/BAS interface requirements.Verify interface with BAS system and confirm metering data to verify compliance.
PV Systems Input to BAS and graphic displaysAs required for Advanced Building Metering and ControlMODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for alarms. Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for power measurements (KW, KVA, Power Factor, KWH), status and alarms. Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for power measurements [KW, KVA, Power Factor, KWH}, status and alarms. Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.YeseMerge Alliance 24VDC Occupied Space StandardDescribe PV system metering/BAS interface requirements.Verify interface with BAS system and confirm indicated metered data to verify compliance.
Automatic Transfer Switches input to BAS and graphic displaysMODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for ATS status (also ethernet for TCP/IP for ATS customized graphical GUI at BAS front end).MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for power measurements (KW, KVA, Power Factor, KWH) status, and alarms. Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for power measurements (KW, KVA, Power Factor, KWH) status, and alarms. Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.Describe ATS/BAS interface requirements.Verify interface with BAS system and confirm indicated metered data to verify compliance.
Standby Generator input to BAS and graphic displaysMODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for generator status and alarms.MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for power measurements (KW, KVA, Power Factor, KWH) and generator status and alarms (NFPA 110 status and alarms).MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for power measurements (KW, KVA, Power Factor, KWH) and generator status and alarms (NFPA 110 status and alarms). Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.Describe Standby Generator/BAS interface requirements.Verify interface with BAS system and confirm indicated metered data to verify compliance.
Uninterruptible Power Systems input to BAS and graphic displaysMODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for alarms (also ethernet for TCP/IP for metering customized graphical GUI at BAS front end).MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for power measurements (KW, KVA, Power Factor, KWH) and alarms. Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for power measurements (KW, KVA, Power Factor, KWH) and alarms. Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.YesDescribe UPS/BAS interface requirements.Verify interface with BAS system and confirm indicated metered data to verify compliance.
Variable Frequency Drives Input to BAS and graphic displaysMODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers.MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers.MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for power measurements (KW, KVA, Power Factor, KWH, Amps, % speed), status( HOA, run, bypass), troubles, and alarms. Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.YesDescribe VFD/BAS interface requirements.Verify interface with BAS system and confirm indicated metered data to verify compliance.
Motor Starters Input to BAS and graphic displaysMODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers.MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers.MODBUS / TCP / IP / BACnet / LonWorks Protocol to match BAS with twisted pair to BAS for monitoring data registers and graphics screens for status (HOA, run), power measurements (KW, KVA, Power Factor, KWH), and alarms. Also ethernet for TCP/IP for metering customized graphical GUI at BAS front end.YesDescribe motor starters/BAS interface requirements.Verify interface with BAS system and confirm indicated metered data to verify compliance.
Additional computer-based BAS interface requirementsDDC using BACnet or LonTalk open communication protocolsIP sensors, thermostats, & devicesWireless selfpowered switches & devicesWireless selfpowered switches & devicesYesYesEnOcean AllianceDescribe BAS interface requirements with switches and devices.Verify interface with BAS system and confirm indicated devices to verify compliance.
Additional computer-based BAS interface requirementsEnergy management & monitoring softwareInterface with smart phones & tabletsInterface with smart phones & tabletsInterface with smart phones & tabletsYesYesProvide BAS interface requirements with smart phones and tablets.Verify interface with BAS system and confirm indicated devices to verify compliance.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Interior Electrical Distribution
Energy saving controls for automatic interruption of non-critical power after operating hoursTime of day scheduling for auto shutdown of task lighting receptacle circuits or integrate occupancy sensors with task lights.Time of Day controllable branch panel breakers for automatic shutdown of computers, displays and task lighting after scheduled hoursIT network smart controls for automatic hot standby after initial period of inactivity & automatic power down after extended period of inactivity. Automatic controls for automatic shutdown of task lighting or time of day scheduling for auto shutdown of task lighting receptacle circuits or integrate occupancy sensors with task lights.YesASHRAE 90.1, LEED M&V StrandardsDescribe scheme for automatic shut down of lighting and computer/display and task lighting circuits.Verify shut down of stated loads after installation of systems to verify control sequences and shut down of stated loads after scheduled hours.
Distribution for Energy MonitoringAs required for Advanced Building Metering and ControlAs required for Advanced Building Metering and Control and to measure individual Energy Cost-saving Measures (ECM) for M&V (KW, KVA Demand, KWH).As required for Advanced Building Metering and Control with meters for separate load types (1. Lighting loads, 2. Receptacle loads, 3. Motor loads (VFD's), 4. Motor loads (Non-VFD's), 5. Central Plant Equipment, and 6. Special purpose rooms, e.g. computer/server rooms. Also to measure individual Energy Cost-saving Measures (ECM) for M&V (KW, KVA Demand, KWH). Panels assigned to tenants shall also be individually metered.As required for Advanced Building Metering and Control with meters for separate load types (1. Lighting loads, 2. Receptacle loads, 3. Motor loads (VFD's), 4. Motor loads (Non-VFD's), 5. Central Plant Equipment, and 6. Special purpose rooms, e.g. computer/server rooms. Also to measure individual Energy Cost-saving Measures (ECM) for M&V (KW, KVA Demand, KWH). Panels assigned to tenants shall also be individually metered.YesASHRAE 90.1, LEED M&V StrandardsDescribe advance building metering requirements.Verify submittals and supplied meter specifications to verify compliance.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Arc- Flash Reduction Maintenance Switches (ARMS) and Arc Flash Barriers
Arc Reduction Maintenance Switches (ARMS)All Switchgear and Main Breaker at Motor Control CentersAll Switchgear and Main Breaker at Motor Control CentersNFPA 70, 70E, NEMA, ULDescribe requirements of arc flash maintenance switches.Verify submittals and shop drawings from manufacturer for supplied units to verify compliance.
Arc- Flash barriers upon insertion of equipmentAll Switchgear Main Breakers and tie breakers.
Motor Control Centers.
All Switchgear Main Breakers tie breakers, and feeder breakers.
Motor Control Centers.
NFPA 70, 70E, NEMA, ULDescribe requirements of arc flash barriers.Verify submittals and shop drawings from manufacturer for supplied units to verify compliance.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Power Factor Correction
95% PFC with harmonic-tuned filters95% PFC with autocontrols and harmonic-tuned filters95% PFC with autocontrols and active harmonic filters98% PFC with autocontrols and active harmonic filtersNFPA 70, NEMADescribe power factor correction requirements.Measure power factor using a power meter to confirm compliance with stated requirements.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Surge Protection Devices
277/480 Volt distribution at Main SwitchgearSPD-2 (250KA)SPD-2 (250KA)SPD-2 (250KA)SPD-2 (250KA)UL 1449 Current EditionDescribe surge protection requirements at main switchgear.Verify submittals and shop drawings from manufacturer for supplied units to verify compliance.
277/480V Volt distribution at Distribution PanelsSPD-2 (160KA)SPD-2 (160KA)SPD-2 (160KA)SPD-2 (160KA)UL 1449 Current EditionDescribe surge protection requirements at distribution panels.Verify submittals and shop drawings from manufacturer for supplied units to verify compliance.
277/480V Volt Branch PanelsSPD-2 (50KA)UL 1449 Current EditionDescribe surge protection requirements at branch panels.Verify submittals and shop drawings from manufacturer for supplied units to verify compliance.
120/208V Volt Branch PanelsSPD-2 (50KA)UL 1449 Current EditionDescribe surge protection requirements at branch panels.Verify submittals and shop drawings from manufacturer for supplied units to verify compliance.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Lightning Protection Systems (LPS)
Lightning Protection Systems Yes where required per NFPA evaluationYes where required per NFPA evaluationYes where required per NFPA evaluationYes where required per NFPA evaluationYesDescribe lightning protection system.Verify submittals and shop drawings from manufacturer for supplied units to verify compliance.
Lightning Protection Systems UL ComplianceUL 96UL 96UL 96UL 96YesUL 96, NFPA 780Describe lightning protection system.Verify submittals and shop drawings from manufacturer for supplied units to verify compliance.
Lightning Protection Systems UL Master Label ComplianceMaster LabelMaster LabelYesUL 96 (Master Label)Describe lightning protection system.Verify submittals and shop drawings from manufacturer for supplied units to verify compliance.
Surge Protection for building service, incoming copper cables and equipment per Master Label RequirementsYesYesYesUL 96 (Master Label)Describe lightning surge protection requirementsVerify submittals and shop drawings from manufacturer for supplied units to verify compliance.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Grounding
Earth counterpoise 5 Ohm to Earth (Engineered system based on earth testing and confirmed by fall-of-potential method.)2 Ohm to Earth (Engineered system based on earth testing and confirmed by fall-of-potential method.)1 Ohm to Earth (Engineered system based on earth testing and confirmed by fall-of-potential method.)YesNFPA 70, IEEE, BICSI/TIADescribe grounding requirements.Measure grounding resistance using fall of potential method per IEEE 81 standard to verify compliance with stated values.
Separate grounding system for Lightning Protection System and single point bond to building counterpoise system.5 Ohm to Earth (Engineered system based on earth testing and confirmed by fall-of-potential method.)5 Ohm to Earth (Engineered system based on earth testing and confirmed by fall-of-potential method.)5 Ohm to Earth (Engineered system based on earth testing and confirmed by fall-of-potential method.)NFPA 70, 780, UL 96Describe grounding requirements.Measure grounding resistance using fall of potential method per IEEE 81 standard to verify compliance with stated values.
Equipment Grounding ConductorsAll low voltage power distribution systems must be supplemented with a separate, insulated ground conductor routed with the phase and neutral conductors.Describe grounding conductor requirementsVerify provision of grounding conductors for each of the low voltage distribution systems.
AttributeBaseline
Tier 1 High Performance
★★
Tier 2 High Performance
★★★
Tier 3 High Performance
Verification
Measurements & VerificationPlans & SpecificationsCalculations & AnalysisReference StandardDesign Basis of DesignConstruction Verification
  Uninteruptible Power Systems (ABS)
EfficiencyDouble conversion efficiency of 95% from 25% to 100% loadDouble conversion efficiency of 95% from 25% to 100% loadIGBT rectifier and IGBT inverter
Double conversion efficiency of 96% from 25% to 100% load
IGBT rectifier and IGBT inverter
Double conversion efficiency of 97% from 25% to 100% load
YesDescribe UPS efficiency requirements.Verify submittals from manufacturer for supplied units to verify compliance.
Power Factor - Output80%80%90%90%YesDescribe UPS output power factor requirements.Measure output power factor using a power meter to confirm compliance with stated requirements.
Power Factor - Input80%80%90%100%YesDescribe UPS input power factor requirements.Measure input power factor using a power meter to confirm compliance with stated requirements.
Input Harmonics<30% current THDRectifier with filters for <7% current THDIGBT rectifier for <5% current THDIGBT rectifier for <5% current THDCertified Representative Factory Test ReportDescribe UPS THD requirements.Measure harmonics using a power meter per IEEE 519 standard to confirm compliance with stated requirements.
^